EM-8466  Rev.5  P. 7 / 7

 

BCD DATA (32-bit data, models: R3-BA32A, BC32A, etc.)

32-bit binary data is used for BCD.
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.

0

15

+0

Lower 16 bits

0

15

+1

Higher 16 bits

 

DISCRETE DATA (models: R3-DA16 and DC16, etc.)

0

15

Input 1   (Output 1)
Input 2   (Output 2)
Input 3   (Output 3)
     :               :
Input 16 (Output 16)

0 : OFF
1 : ON 

Содержание R3-NEIP1

Страница 1: ... ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temperature must be within 10 to 55 C 14 to 131 F with relative humidity within 30 to 90 RH in order to ensure adequate life...

Страница 2: ...e position to specify how many data areas four types are to be occupied by each Two bits from SW1 and SW2 are assigned to each posi tion and data areas can be specified from the module No 1 through 8 Setting for No 9 and later modules is identical to No 8 SW ASSIGNMENT MODULE NO SW1 1 SW1 2 1 SW1 3 SW1 4 2 SW1 5 SW1 6 3 SW1 7 SW1 8 4 SW2 1 SW2 2 5 SW2 3 SW2 4 6 SW2 5 SW2 6 7 SW2 7 SW2 8 8 SW SETTI...

Страница 3: ... 255 255 192 168 0 1 TERMINAL CONNECTIONS Connect the unit as in the diagram below EXTERNAL DIMENSIONS unit mm inch 1 2 3 4 5 6 130 5 12 27 5 1 08 109 4 29 POSITIONING GUIDE TERMINAL COVER 6 M3 SCREW 6 2 24 CONNECTION DIAGRAM INTERNAL POWER INTERNAL BUS CONFIGURATION JACK JACK RJ 45 MODULAR JACK BUS CONNECTOR 1 RUN RUN RUN CONTACT OUTPUT EtherNet IP 4 WIRING INSTRUCTIONS M3 SCREW TERMINAL Torque 0...

Страница 4: ...s C WINDOWS ping Enter IP address in decimal ping with 32 bytes of data Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Ping statistics for Packets Sent 4 Received 4 Lost 0 0 loss Replies in case of normal connection are as shown above If the connection cannot be established normally due to e g wron...

Страница 5: ...le 3 Module 4 Module 5 Module 6 Module 7 Module Status Error Status Data Error Status Begin Address 0 15 0 2 4 6 8 10 12 14 Module 1 Module 2 Module 3 Module 4 Module 5 Module 6 Module 7 Begin Address The area enclosed with bold line is assigned for I O data 249 251 249 251 16 16 Module Status Error Status and Data Error Status are assigned to the last three words of the output data respectively E...

Страница 6: ...nge represented in 2 s complement 0 15 TEMPERATURE DATA 16 bit data models R3 RS4 TS4 and US4 etc 16 bit binary data With C temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature unit the integer section of raw data is directly converted into the data For example 135 4 F is con verted into 135 Minus temperature is converted into negative values re...

Страница 7: ... 7 7 BCD DATA 32 bit data models R3 BA32A BC32A etc 32 bit binary data is used for BCD Lower 16 bits are allocated from the lowest address to higher ones higher 16 bits in turn 0 15 0 Lower 16 bits 0 15 1 Higher 16 bits DISCRETE DATA models R3 DA16 and DC16 etc 0 15 Input 1 Output 1 Input 2 Output 2 Input 3 Output 3 Input 16 Output 16 0 OFF 1 ON ...