background image

R3-ND1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8353  Rev.14  P. 3 / 6

PC CONFIGURATOR

The following parameter items can be set with using PC Configurator Software (model: R3CON).
Refer to the users manual for the R3CON for detailed operation of the software program.

 

NETWORK MODULE SETTING 

PARAMETER

SETTING RANGE

DEFAULT SETTING

Time (no communication time)

0.2 – 3200.0 (sec.)

3.0 (sec.) 

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

 

EXTERNAL DIMENSIONS  unit: mm (inch) 

1

2

3

4

5

6

130 (5.12)

27.5 (1.08)

109 (4.29)

POSITIONING

GUIDE

TERMINAL

COVER

6–M3

SCREW

6.2

(.24)

 

CONNECTION DIAGRAM

Note:  In order to improve EMC performance, bond the FG 

terminal to ground.

Caution: FG terminal is NOT a protective conductor terminal.

INTERNAL

POWER

INTERNAL

BUS

CONFIGURATION JACK

JACK

BUS CONNECTOR

*

Not provided with ‘No Power Supply’ type module.

1

4

RUN 

+

RUN 

RUN CONTACT OUTPUT

2

3

6

U (+) 

V (–) 

FG

POWER INPUT

*

V+

CAN_H

Drain
CAN_L

V–

To Other

DeviceNet

Devices

*

WIRING INSTRUCTIONS

 

M3 SCREW TERMINAL (power input, RUN contact output) 

Torque: 0.5 N·m

 

SOLDERLESS TERMINAL 

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.  Solder-
less terminals with insulation sleeve do not fit.
Recommended manufacturer: Japan Solderless Terminal 
MFG.Co.Ltd, Nichifu Co.,ltd
Applicable wire size: 0.75 to 1.25 mm

2

12max

6max

3max

4min

3.2 dia.

(mm)

 

EURO TYPE CONNECTOR TERMINAL (DeviceNet)

Applicable wire size: 0.2 to 2.5 mm

2

 (AWG24 to 12)

Stripped length: 7 mm

Отзывы: