R3-BSW

P. 1 / 3

EM-8357 Rev.7

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

Phone: +81(6)6659-8201   Fax: +81(6)6659-8510   E-mail: [email protected]

INSTALLATION BASE

(free I/O address) 

MODEL

R3-BSW

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 PACKAGE INCLUDES:

 Base ............................................................................... (1)

 MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 CONFORMITY WITH EU DIRECTIVES

• The  equipment  must  be  mounted  inside  the  instrument 

panel of a metal enclosure.

• The actual installation environments such as panel con

-

figurations, connected devices and connected wires may 
affect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure CE conformity.

 GENERAL PRECAUTIONS

• Before you remove the base or mount it, turn off the power 

supply for safety.

 ENVIRONMENT

• Indoor use
• When heavy dust or metal particles are present in the air, 

install the unit inside proper housing with sufficient ven-
tilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C     

(14 to 131°F) with relative humidity within 30 to 90% RH 

in order to ensure adequate life span and operation.

 WIRING

• Do  not  install  cables  close  to  noise  sources  (relay  drive 

cable, high frequency line, etc.).

• Do  not  bind  these  cables  together  with  those  in  which 

noises are present.  Do not install them in the same duct.

FRONT VIEW

I/O 1

I/O 2

I/O n

8

67

3

4

5

2

1

0

F

E

D

C B

A 9

SW1

8

67

3

4

5

2

1

0

F

E

D

C B

A 9

SW2

8

67

3

4

5

2

1

0

F

E

D

C B

A 9

SWn–1

8

67

3

4

5

2

1

0

F

E

D

C B

A 9

SWn

 

I/O MODULE ADDRESS

Free I/O module address can be assigned to each module po

-

sition using the rotary switch, within 1 to 16.  Every module 
can be mounted on any position.
Switch positions and addresses correspond to each other as 
shown below:

I/O module address

Rotary switch position

1

0

2

1

:

:

n

n – 1

:

:

16

F

DO NOT assign one address to more than one I/O module to 

ensure adequate operations and to prevent failures.
In case of power supply module, interface module, they op-
erate normally even address is conflicted.

For a power supply module, be sure to install in the right 

end slot or left end slot for heat dissipation.  In the case of 
redundant power supply, consecutively install them in the 
right end slot or left end slot.

Example for R3-BSW04

I/O module address

Rotary switch position

4

3

1

2

Power

Supply

Module

Interface

Module

I/O

Module

I/O

Module

3

2

0

1