M-system R3-AS8 Скачать руководство пользователя страница 4

R3-AS8

P. 4 / 4

EM-8440 Rev.1

M-SYSTEM WARRANTY

M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System's sole liability, and purchaser's exclusive remedies,
under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty.  To
submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.  M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]

OUTPUT DATA DESCRIPTIONS

Four alarm setpoints are selectable per each input.  Two (2)
word (16 bits 

×

 2) data is transmitterd to the PLC or the host

device via the R3 network module.

ALARM SETTING

The following parameters are programmable using the PC
Configurator Software (model: R3CON).

ALARM TRIP POINT (-15.00 to +115.00%)

Four alarm setpoints are selectable per each input.

ALARM TYPE (High or Low)

High or Low alarm is selectable for each alarm trip point.
High alarm: An alarm is set when the input signal goes above
the setpoint.
Low alarm: An alarm is set when the input signal goes be-
low the setpoint.

DEADBAND (HYSTERESIS)

   (0.00 to 100.00%; factory set to 5.00)

Deadband (deviation between the points where the alarm is
set and reset) is selectable for each alarm trip point.

POWER ON DELAY TIME

   (0.0 to 99.0 seconds; factory set to 5.0)

The alarm output start functioning in the preset time after
the power has been turned on.
This setting is common to all four points.

ALARM ON DELAY TIME

   (0.0 to 99.0 seconds; factory set to 1.0)

The alarm output is set when the preset time elapses after
the input has entered in the alarm range.
This setting is common to all four points.

ALARM HOLD TIME

   (0.0 to 99.0 seconds; factory set to 1.0)

The alarm output is held for the preset time even if it is
reset in shorter time.
This setting is common to all four points.

0

15

Alarm 1
Alarm 2

Input 1

Alarm 3
Alarm 4

Alarm 1
Alarm 2

Input 2

Alarm 3
Alarm 4

Alarm 1
Alarm 2

Input 3

Alarm 3
Alarm 4

Alarm 1
Alarm 2

Input 4

Alarm 3
Alarm 4

0

15

Alarm 1
Alarm 2

Input 5

Alarm 3
Alarm 4

Alarm 1
Alarm 2

Input 6

Alarm 3
Alarm 4

Alarm 1
Alarm 2

Input 7

Alarm 3
Alarm 4

Alarm 1
Alarm 2

Input 8

Alarm 3
Alarm 4

0

+1