DATA ADDRESS
ADDRESS
DATA FORMAT
NAME
Coil (0X)
1 – 32
bit
DO: Alarm (Only Address 10001 is enabled.)
33 – 40
bit
Cold junction compensation SW (0: Disable, 1: Enable) *
1
Input Status (1X)
1 – 32
bit
DI: Trigger contact input (Only Address 10001 is enabled.)
33 – 40
bit
ADC overrange
Input Register (3X)
1 – 8
I
AI per channel in engineering unit (DC: × 1000, TC: × 10)
17 – 32
F
AI per channel in engineering unit
33 – 48
F
Calibrated voltage value
49 – 64
F
Cold junction temperature *
2
65 – 72
F
Temperature measured at Ch.1 thr. 4
81 – 88
I
Channel status
513
I
Bit
System Status
0 to 5
Reserved for system use
6
E
2
PROM diagnostics (0: Normal, 1: Error)
7
ADC error (0: Normal, 1: Error)
8 to 15 Reserved for system use
514 – 521
B16
Model No.
522 – 529
B16
Serial No.
530 – 537
B16
Hardware version No.
538 – 545
B16
Firmware version No.
Holding Register (4X)
49 – 50
F
Input filter time constant (seconds) *
3
145 – 152
I
I/O type No
514
I
Burnout type (0: No burnout, 1: Upscale, 2: Downscale) *
1
515
I
Line noise filtering type (0: 50/60 Hz, 1: 50 Hz, 2: 60 Hz) *
1
bit =1bit, I = 16-bit integer, F = 32-bit floating, B16 = 16-byte character
*1. Changeable only when the mode SW is set to 0 for R1MS-GH3.
*2. Thermocouple input only.
*3. Effective for large noise in the input signal. 0 sec. = No Filtering
Sign
Address n+1
• 32-bit Floating
Address n
Exponent
Mantissa
■
INPUT DATA