background image

MODEL: R1M-GH

Remote I/O R1M Series

THERMOCOUPLE & DC INPUT MODULE

(16 points)
Functions & Features
• 16-point thermocouple or DC inputs
• Easy system expansion via Modbus RTU

40
(1.57)

115

(4.53)

mm (inch)

175 (6.89)

MODEL: R1M-GH2T-[1]

ORDERING INFORMATION

• Code number: R1M-GH2T-[1]
Specify a code from below for [1]
e.g. R1M-GH2T-M2

FIELD TERMINAL TYPE

T: M3 screw terminals

[1] POWER INPUT

AC Power

M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
 47 – 66 Hz)

DC Power

R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

RELATED PRODUCTS

• Resistor module (model: REM3-250)
• R1X configurator software (model: R1CON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC.  Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.

GENERAL SPECIFICATIONS

Connection
  Power input, transmission: Euro type connector terminal
  RS-232-C: 9-pin D-sub connector (male)
  I/O: M3 screw terminals
Isolation: Input to RS-232-C or RS-485 to power
Address setting: Rotary switch; 1 – F (15 nodes)

RUN indicator LED: Green light blinks in normal conditions.

COMMUNICATION

Baud rate: 38.4 kbps
Communication: Half-duplex, asynchronous, no procedure
Protocol: Modbus RTU
Protocol: Modbus RTU
Refer to Modbus Protocol Reference Guide (EM-5650) for
supported functions.
■ RS-232-C
Standard: Conforms to RS-232-C, EIA
Transmission distance: 10 meters max.
■ RS-485
Standard: Conforms to RS-485, EIA
Transmission distance: 500 meters max.
Transmission media: Shielded twisted-pair cable (CPEV-S
0.9 dia.)

INPUT SPECIFICATIONS

Input: Thermocouple or DC input, 16 points
(Common negative for DC input)
Measuring Range:
  ±20 V, ±5 V, ±1 V, ±0.8 V, ±0.2 V, ±50 mV, ±10 mV
Input resistance: 300 kΩ
Thermocouple types: PR, K, E, J, T, B, R, S, C, N, U, L, P
Sampling rate: 100 millisec./16 points
• Trigger input: Dry contact; ON detected at ≤1.5 V
Sensing: Approx. 5 V DC @ 1 mA

INSTALLATION

Power Consumption
•AC: Approx. 10 VA
•DC: Approx. 7 W
Operating temperature: -5 to +60°C (23 to 140°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 400 g (0.88 lbs)

PERFORMANCE (% of measuring range)

Accuracy
DC input: ±0.3 %
Thermocouple input: See the table on the end of this
section.
Cold junction compensation error: ±3°C or ±5.4°F max.
(at 20°C ±10°C or 68°F ±18°F)
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
±0.05 %/°C (±0.03 %/°F) for 10 mV range
Insulation resistance: ≥100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute (input to RS-232-
C or RS-485 to power to ground)

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Содержание R1M Series

Страница 1: ...rotocol Modbus RTU Protocol Modbus RTU Refer to Modbus Protocol Reference Guide EM 5650 for supported functions RS 232 C Standard Conforms to RS 232 C EIA Transmission distance 10 meters max RS 485 St...

Страница 2: ...700 C or 1292 F The described accuracy may be partially not satisfied when the temperature ranges below 0 C STANDARDS APPROVALS CE conformity EMC Directive 2004 108 EC EMI EN 61000 6 4 2007 EMS EN 61...

Страница 3: ...e When the device is not at the end remove the jumper pin Remark 1 This device is not designed to cancel noise included in the input signals Be careful to eliminate such noise by using shielded cables...

Страница 4: ...slave 04 Read Input Registers X Collected data from the field by the slave 05 Force Single Coil X Digital output from the slave 06 Preset Single Registers X General purpose register within the slave...

Страница 5: ...17 48 F Reserved for AO in engineering unit 145 160 Y Y I I O type No 161 176 Y I Burnout type 161 168 for Type J3 0 No burnout 1 Upscale 2 Downscale 4 I 16 bit integer F 32 bit floating B16 16 byte...

Страница 6: ...E A D DATA Decimal DC 20V 20000 5V 5000 1V 10000 0 8V 8000 0 2V 20000 50mV 5000 10mV 10000 Thermocouple Temperature x 10 RTD Temperature x 10 Potentiometer 0 100 2000 0 500 0 1k 0 10k BIT NAME DESCRIP...

Страница 7: ...00 to 600 C 0X1B L 200 to 900 C 0X1C P Platinel II 0 to 1395 C R1M J3 RTD input 0X30 JPt 100 JIS 89 200 to 500 C 0X31 Pt 100 JIS 89 200 to 660 C 0X32 Pt 100 JIS 97 IEC 200 to 850 C 0X33 Pt 50 JIS 81 2...

Страница 8: ...istance between the PC and the R1Ms is long insert an RS 232 C RS 485 Converter for isolation RS 232 C RS 232 C RS 485 Converter model R2K 1 Specifications are subject to change without notice Ruggh l...

Страница 9: ...urce connected to the unit and TDK Model ZCAT3035 1330 or equivalent for the RS 232C cable are recommended The equipment must be installed such that appropriate clearance and creepage distances are ma...

Страница 10: ...5 T1 T2 T3 T4 T5 T6 T7 CJC Sensor model CJM RS 485 Connector Address Setting Rotary SW Configurator Jack Specifications Marking Power Terminals RS 232C 9 pin Connector RUN Indicator LED DIN Rail Adapt...

Страница 11: ...t the end remove the jumper pin Remark 1 This device is not designed to cancel noise included in the input signals Be careful to eliminate such noise by using shielded cables Remark 2 Be sure to maint...

Страница 12: ...alibration procedure is explained below CALIBRATION Warm up the unit for at least 10 minutes Apply 0 25 50 75 and 100 input signal Check that the output signal for the respective input signal remains...