MODEL: R1M-GH

R1M-GH SPECIFICATIONS

ES-5657 Rev.11   Page 7/9

 INPUT REGISTERS DESCRIPTION

(1) ANALOG INPUT IN % (30001 to 30016; 30001 to 30008 for J3)

Indicates analog input values in percentage for each channel (1 – 16; 1 – 8 for J3).

(2) ANALOG INPUT IN ENGINEERING UNIT (30017 to 30048; 30017 to 30032 for J3)

Indicates analog input values in engineering unit for each channel (1 – 16; 1 – 8 for J3). The unit is specific to each input type: °C
for temperature, Volts for voltage, and % for potentiometer. The data are 32-bit floating values, which requires two consecutive
registers for one module.

(3) CHANNEL STATUS (30081 to 30096)

Indicates the current status of analog inputs (1 – 16; 1 – 8 for J3). The following list shows the names and descriptions of each bit.

INPUT TYPE & RANGE 

A/D DATA (Decimal)

DC

±20V

±20000 

 

 

 

±5V

±5000 

 

 

 

±1V

±10000 

 

 

 

±0.8V

±8000 

 

 

 

±0.2V

±20000 

 

 

 

±50mV

±5000 

 

 

 

±10mV

±10000

Thermocouple 

 

Temperature x 10

RTD

Temperature x 10

Potentiometer 

0 – 100Ω

±2000 

 

 

 

0 – 500Ω

 

 

 

 

0 – 1kΩ

 

 

 

 

0 – 10kΩ

BIT 

NAME 

DESCRIPTION

 

Input Overrange

Indicates the designated analog input is in overrange, defined as one or

 

 

 

more of the following condition:

 

 

 

• ADC input value 0X0000 or 0XFFFF

 

 

 

• Burnout status for thermocouple input

 

 

 

• Out of range defined in the temperature table (thermocouple and RTD)

 

 

 

• ADC error

 

 

 

0 : Normal

 

 

 

1 : Overrange

 

ADC Error

Indicates the status of ADC.

 

 

 

0 : Normal

 

 

 

1 : Error

 

12 

Cold Junction Compensation SW 

Indicates whether the cold junction compensation is enabled or disabled, for

 

 

 

thermocouple input.

 

 

 

0 : Disable

 

 

 

1 : Enable

 

Others 

Reserved 

For system’s use

Содержание R1M-GH2T Series

Страница 1: ...r for applicable cable types GENERAL SPECIFICATIONS Connection Power input transmission Euro type connector terminal RS 232 C 9 pin D sub connector male Lock screw No 4 40 UNC I O M3 screw terminals I...

Страница 2: ...1000 454 to 1832 0 7 J IC 210 to 1200 346 to 2192 0 7 T CC 270 to 400 454 to 752 1 0 B RH 100 to 1820 212 to 3308 0 7 2 R 50 to 1760 58 to 3200 0 7 1 S 50 to 1760 58 to 3200 0 7 1 C WRe 5 26 0 to 2320...

Страница 3: ...RD 3 Received Data AB SG 5 Signal Common CB CS 7 Clear to Send CA RS 8 Request to Send 1 Not Used 4 DO NOT connect Connecting may 6 cause malfunctions 9 1 5 6 9 RS 232 C INTERFACE MODBUS WIRING CONNEC...

Страница 4: ...not at the end remove the jumper pin Remark 1 This device is not designed to cancel noise included in the input signals Be careful to eliminate such noise by using shielded cables Remark 2 Be sure to...

Страница 5: ...ted data from the field by the slave 05 Force Single Coil X Digital output from the slave 06 Preset Single Registers X General purpose register within the slave 07 Read Exception Status 08 Diagnostics...

Страница 6: ...dware version No 538 545 Y Y Y Y B16 Firmware version No Holding Register 1 16 I Reserved for AO in 4X 17 48 F Reserved for AO in engineering unit 145 160 Y Y I I O type No 161 176 Y I Burnout type 16...

Страница 7: ...inputs 1 16 1 8 for J3 The following list shows the names and descriptions of each bit INPUT TYPE RANGE A D DATA Decimal DC 20V 20000 5V 5000 1V 10000 0 8V 8000 0 2V 20000 50mV 5000 10mV 10000 Thermoc...

Страница 8: ...0 C 0X16 R 50 to 1760 C 0X17 S 50 to 1760 C 0X18 C WRe 5 26 0 to 2320 C 0X19 N 270 to 1300 C 0X1A U 200 to 600 C 0X1B L 200 to 900 C 0X1C P Platinel II 0 to 1395 C R1M J3 RTD input 0X30 JPt 100 JIS 89...

Страница 9: ...5 TC DC Inputs model R1M GH Contact Inputs model R1M A1 Contact Outputs model R1M D1 When the cable distance between the PC and the R1Ms is long insert an RS 232 C RS 485 Converter for isolation RS 23...

Отзывы: