FRONT VIEW & PROGRAMMING
■
PROGRAMMING PROCEDURE
1) Press ITEM UP or DOWN key until ITEM display indicates “01”.
2) Press DATA UP or DOWN key and choose “2” on DATA display.
1: Data indication only.
2: All parameters are modifiable.
3) Press ITEM UP or DOWN key until ITEM display shows the
ITEM No. you need to change.
4) Press DATA UP or DOWN key and choose a DATA No. or value
you need on DATA display.
5) Repeat above 3 and 4. (Entered data is stored 1 sec. after the
operation has been complete.)
6) Press ITEM UP or DOWN key until ITEM display indicates “01”.
7) Press DATA UP or DOWN key and choose “1” on the display.
8) Press ITEM UP or DOWN key until ITEM display indicates “P”.
DATA display shows process input. You can now check data set-
ting by choosing ITEM No.
Note : DO NOT press UP and DOWN keys simultaneously.
ITEM
MDF.
CODE
DATA
CONTENTS
DEFAULT
P
N/A
-9999 – 9999
Input display in engineering unit *
1
---
01
1, 2, 3
Modification code
1 : Data indication only.
2 : All parameters are modifiable.
3 : Only ITEM 19 is modifiable.
1
02
N/A
0 – 99
Status indication (“0” is normally indicated.)
---
03
2
0 – 12
Thermocouple type
0: (PR), 1: K (CA), 2: E (CRC), 3: J (IC), 4: T (CC), 5: B (RH),
6: R, 7: S, 8: C (WRe 5-26), 9: N, 10: U, 11: L, 12: P (Platinel II)
1: K (CA)
04
N/A
0, 1, 2
Output range code
0 : V1 (-1 – +1V)
1 : V2 (-10 – +10V)
2 : Z1 (0 – 20mA)
V1 : 0
V2 : 1
Z1 : 2
05
N/A
-15.0 – 115.0
Input indicated in % (of the range set in ITEM 13/14)
---
06/L
2
-15.0 – 115.0
Output indicated in % with ITEM 01 DATA 1 (of the range set in ITEM 15/16)
Loop test output with ITEM 01 DATA 2 (‘L’ is indicated as ITEM No.)
(Use DATA UP/DOWN key to set the output signal.)
---
07
2
-99.99 – 99.99
Zero adjustment (%) (fine adj. of the value set in ITEM 15)
0.00
08
2
0.000 – 9.999
Gain adjustment (fine adj. of the value set in ITEM 16)
1.000
09
2
0, 1, 2
Temperature unit
0: °C
1: °F
2: K
0
10
2
0, 1, 2, 3, 4
Moving average (sampling cycle: 10 msec.)
0: No
1: 4 samples
2: 8 samples
3: 16 samples
4: 32 samples
0
11
2
0, 1 – 60
Power-saving mode
0 : Continuous display
1 – 60 : Time before display turned off (minutes)
10
12
2
0, 1
Burnout protection
0 : Downscale
1 : Upscale
1
13
14
2
2
-270.0 – 2410
-270.0 – 2410
Lower range temperature (ITEM 13 < ITEM 14) *
1
Upper range temperature (ITEM 13 < ITEM 14) *
1
0.0
100.0
15
16
2
2
-1.00 – 1.00
-1.00 – 1.00
Output code V1
0% output voltage (V) *
2
100% output voltage (V) *
2
-1.00
1.00
15
16
2
2
-10.0 – 10.0
-10.0 – 10.0
Output code V2
0% output voltage (V) *
2
100% output voltage (V) *
2
-10.0
10.0
15
16
2
2
0.0 – 20.0
0.0 – 20.0
Output code Z1
0% output current (mA) *
2
100% output current (mA) *
2
4.0
20.0
17
2
0, 1
Output characteristic 0: Positive
1: Negative (inverted output)
0
18
3
0, 1
Reset all settings *
3
0
19
N/A
---
ROM version
---
*1 : According to the temperature unit specified in ITEM 09. For under -1000 or over 1000 values, under decimal point position cannot
be displayed and setting is unavailable.
*2 : ITEM 15 < ITEM 16.
*3 : Press DATA UP key and choose DATA 1. Double-click DATA DOWN key. The display shows DATA 0 after the initialization is
complete.
PL4
PL3
PL2
PL1
DATA
ITEM
DATA
ITEM
ITEM No. Display
DATA UP-DOWN Keys
ITEM No. UP-DOWN Keys
DATA Display
Status LED
Polarity LED