MODEL: MXCB

MXCB SPECIFICATIONS

ES-1745 Rev.6   Page 5/6

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

Isolation

1

7 U(+)

V(–)

8

POWER

+

OUTPUT

2

D/A

Converter

Digital

Computation

Base Socket

DATA

ITEM

5

3

4

10

11

UP

9

From SOFT-TERMINAL

DOWN

COM

STOP

From COMPUTER

6

UP

DOWN

COM

Control Input Ci

rcuit

Effective only
in MAN mode

FUNCTIONS

 

COMMAND 

TERM. 

SIGNAL STATUS

UP

3 – 6 

1  0  0  1  –  –  –  –

Computer 

DOWN 

4 – 6 

0  1  0  1  –  –  –  –

STOP 

5 – 6 

1  1  1  1  0  0  0  0

ST/STL

 

UP 

9 – 11  –  –  –  –  1  0  0  1

DOWN 

10 – 11  –  –  –  –  0  1  0  1

Output of the MXCB 

1 – 2

↑ ↓

  H  H 

↑ ↓

  H  H

[Keys] 1  : ON 

0  : OFF 

–  : ON or OFF

 

H  : Hold

  : Increase

  : Decrease

• 

MXCB Used Independently

In normal operating mode, the MXCB responds to  UP/DOWN signals 
from the computer in the preset ramp rate. If the computer fails, this will 
be detected as a “STOP”  command and output will be held at the value 
prior to the breakdown. You can increase the output signal by closing 
across the terminals 9 – 11, and decrease it by closing 10 – 11. The output 
responds in the preset ramp rate.

• 

MXCB Used in Combination with ST/STL

In normal operating mode, the MXCB responds to UP/DOWN signals 
from the computer in the preset ramp rate. If the computer fails, the 
“STOP”  command will override computer output and put the unit in the 
manual operation mode by the ST/STL.  Using the top-mounted UP or 
DOWN key, output can be increased or decreased in the preset ramp rate. 
Output signal value can be read on the top-mounted indicator. 
For more precise control, use the monitor terminals. Also the computer 
input can be overridden with the AUTO/MANUAL selector on the 
Soft-Terminal. This is useful when you need to change the output quickly 
during automatic operation by the computer control.

DEFAULT SETTING

Содержание MXCB-1

Страница 1: ... 150 V ripple 10 p p max 3 OPTIONS blank none Q With options specify the specification SPECIFICATIONS OF OPTION Q EX FACTORY SETTING SET Preset according to the Ordering Information Sheet No ESU 1745 RELATED PRODUCTS Soft Terminal model ST STL GENERAL SPECIFICATIONS Construction Plug in Connection M3 5 screw terminals Housing material Flame resistant resin black Isolation Input to output to power ...

Страница 2: ...to 131 F Operating humidity 30 to 90 RH non condensing Mounting Surface or DIN rail Weight 450 g 0 99 lb PERFORMANCE in percentage of max span Display accuracy Accuracy 1 digit with 0 0 100 0 scaling Temp coefficient 0 015 C 0 008 F Accuracy 0 1 Min span required to ensure the accuracy 20 of the nominal output range Response time Approx 1 999 sec variable 0 100 Output memory at power OFF E 2 PROM ...

Страница 3: ...UP DOWN Keys DATA Display DOWN LED UP LED STOP LED Polarity LED Refer to the instruction manual for detailed procedures CONNECTION EXAMPLES Used Independently AUTO OUTPUT AUTO OUTPUT OUTPUT OUTPUT COMPUTER FAILURE 9 10 11 5 6 2 1 3 4 POWER 7 8 E P 4 20mA DC MXCB FIELD CONTROL VALVE FLOWMETER COMPUTER PANEL FRONT BACK UP DOWN FEEDBACK SIGNAL STOP ...

Страница 4: ...COMPUTER FAILURE 9 10 11 5 6 2 1 3 4 POWER 7 8 E P 4 20mA DC FEEDBACK SIGNAL ST STL MXCB FIELD CONTROL VALVE FLOWMETER COMPUTER PANEL FRONT BACK STOP UP DOWN AUTO OUTPUT AUTO OUTPUT EXTERNAL DIMENSIONS TERMINAL ASSIGNMENTS unit mm inch 80 3 15 50 1 97 103 4 06 132 5 20 20 79 When mounting no extra space is needed between units 5 6 7 8 2 1 11 10 3 3 13 80 3 15 40 1 57 50 1 97 7 8 31 CLAMP top botto...

Страница 5: ...TOP command and output will be held at the value prior to the breakdown You can increase the output signal by closing across the terminals 9 11 and decrease it by closing 10 11 The output responds in the preset ramp rate MXCB Used in Combination with ST STL In normal operating mode the MXCB responds to UP DOWN signals from the computer in the preset ramp rate If the computer fails the STOP command...

Страница 6: ...p with Multiplex Transmission E P MX COMPUTER Control Valve E P MX COMPUTER Control Valve Computer Backup Sta MXCB Computer Backup Sta MXCB Soft Terminal ST E P COMPUTER Control Valve Flowmeter MX Computer Backup Sta MXCB Soft Terminal STL Controller E P MX REMOTE I O Control Valve Computer Backup Sta MXCB E P MX Control Valve MXCB E P MX Control Valve COMPUTER Flowmeter Flowmeter Flowmeter SYSTEM...