background image

MSP4 / MSP5 / MSP6

P.  / 7

EM-4854 Rev.8

OFF

1

2

3

4

ON

PWR

INP

ALM

DLY

ZERO

SPAN

DZ

Insulation Barrier

Fuse

Connector

SW1

ZERO
SPAN
DZ
DLY
SW1

PWR
INP
ALM

: Zero Adjustment
: Span Adjustment
: Deadband Adjustment
: Restarting Timer
: Direct/Reverse Actions,
  Operation at Abnormally Low Input
: Power Indicator (green with power supplied)
: Input Indicator (green with input applied)
: Status Indicator (red flashes in 2 sec. intervals,
  flashes in 0.5 sec. intervals with mechanical lock detected) 

Remark:  Turning adjustment potentiom-
eters and switches with a torque exceed-
ing their tolerance may destroy their 
stoppers.
Turn them carefully and stop where they 
hit the stoppers.  Be careful especially 
with Re-starting timer adjustment.

Figure 3.  MSP Control PCB Identification

OUTPUT SPAN ADJUSTABILITY

The servo-control circuit compares and amplifies input sig-
nal (setpoint) and feedback signal from a potentiometer, and 
drives the motor to such direction to minimize difference of 
the two signals.

0

25

50

75

100

25

50

75

100

0

INPUT SIGNAL (%)

STEM POSITION (%)

Span Counterclockwise

Zero Clockwise

Zero Counterclockwise

Span Clockwise

Adjustable Zero Range

Adjustable Span Range

Figure 4.  I/O Characteristics (Adjustable Range)

Table 1.  Available Stroke Range for Each Model
 

MODEL 

L

 

MIN. STROKE  MAX. STROKE

 

MSP4-1 

29 

  5 

10 

 

 

MSP4-2 

34 

  8 

15

 

MSP5-1 

40 

  5 

10 

 

 

MSP5-3 

50 

10 

20

 

MSP6-3 

58 

10 

20 

 

 

MSP6-4 

78 

20 

40

Figure 5.  Minimum & Maximum Stroke

Maximum Stroke

Minimum

Stroke

L

Yoke Surface

MANUAL OPERATION FUNCTION

(for MSP4 AC power supply)

1)  Be sure to turn OFF the power voltage. It may result in 

electrical shock or system breakdown, if operating while 
the power applied. 

2)  Remove the cap on the cover top using a 22 mm wrench.
3)  Insert the attached hexagon key wrench in the manual 

drive shaft as shown in figure.

4)  The  wrench  turning  direction  differs  according  to  the 

model. 

MODEL

STROKE/ROTATION

[mm/turns]

TURNING DIRECTION 

LOOKING FROM TOP 

COVER

MSP4-x3

1/27 

CCW/EXTEND

MSP4-x4

1/54

CCW/RETRACT

MSP4-x7

1/112

CCW/EXTEND

5)  Tighten  the  cap  on  the  cover  with  4  to  6  N

·

m  torque. 

Turning  the  torque  in  excess  may  damage  the  screw 
thread of the cap.

Note:  The  manual  operation  function  is  not  available  for 
24V DC power model.

Cap

Hexagon key wrench

O ring

Cover

Drive shaft

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Содержание MSP5

Страница 1: ...emale thread 1 0 pitch 1 M10 female thread 1 25 pitch D M6 female thread 1 0 pitch E M8 female thread 1 25 pitch F M10 female thread 1 5 pitch 4 SEQUENTIAL CONTROL SIGNALS L Full open closed signal F Forced open close signal B Full open closed and forced open close signals Select With Terminal Box 0 Without 5 TERMINAL BOX T With 0 Without 6 INPUT Current A 4 20 mA DC Input resistance 250 Ω Z Speci...

Страница 2: ...0 mm 300 N 67 lbs MSP5 x7 18 sec 10 mm 700 N 157 lbs Position Output 1 5 V DC not isolated With direct action 5 1 V DC position output is provided proportionally to 4 20 mA DC 1 5 V DC input Load resistance 5 kΩ Full open closed signals Limit switch contact Rating 125 V AC 0 75 A cos ø 1 30 V DC 0 6 A resistive load Mechanical life 3 10 7 cycles Maximum operation frequency 60 cycles min INSTALLATI...

Страница 3: ...or above 100 Limiters are set at approx 1 5 for the full closed side approx 101 5 for the full open side Seal Spring The Mini top Series incorporates a seal spring to maintain the sealing pressure when the valve is fully closed The standard spring has 0 5 1 mm 02 04 flexibility to facilitate the full closed adjustment TERMINAL CONNECTIONS black 1 U V COM1 COM2 COM1 white 2 red 3 green 4 yellow 5 b...

Страница 4: ... M10 1 25 15 D M 6 1 0 E M 8 1 25 F M10 1 5 42 1 65 43 1 69 67 2 64 85 3 35 34 1 34 141 5 55 181 7 13 90 3 54 130 5 12 98 3 86 50 1 97 max 46 1 81 dia 4 M5 10 39 deep 31 1 22 2 08 36 0 1 dia 0 66 2 60 dia M See the table to the right YOKE CONNECTION for AC power supply 40 1 57 max with 5 10 mm stroke YOKE SURFACE 20 79 60 2 36 35 1 38 7 5 30 2 G 1 2 CONDUIT 32 5 1 28 Cable connector or leadwires n...

Страница 5: ...COM2 FULL OPEN or FULL CLOSED SIGNAL POSITION OUTPUT 1 5V DC POWER MODE SELECTOR POWER INPUT STATUS POT MOTOR LIMIT SW Full open closed signals and forced open close signals are optional Disregard the switching regulator circuit for DC power input Specifications are subject to change without notice Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com ww...

Страница 6: ...ce Observe at the minimum of 15 centimeters 6 inches above the cover OUTDOOR USE When installing the MSP outdoor or where it is exposed to rain or water drops be sure to fasten the cable connector tightly and leave a slack of the cable Do not mount the MSP in such direction that the output stem or cable connector is at the top of the MSP unit ELECTRICAL CONNECTION With DC power type unit power sup...

Страница 7: ... new fuse is melted again soon after it has been re placed there may be problems with the control PCB or the motor Contact M System or sales representative RE STARTING TIMER The MSP is equipped with a timer circuit which gives an interval period 0 10 sec between stop restart actions to prevent the motor and other internal components from overheating It is recommended to set a long restarting time ...

Страница 8: ...n Clockwise Adjustable Zero Range Adjustable Span Range Figure 4 I O Characteristics Adjustable Range Table 1 Available Stroke Range for Each Model MODEL L MIN STROKE MAX STROKE MSP4 1 29 5 10 MSP4 2 34 8 15 MSP5 1 40 5 10 MSP5 3 50 10 20 MSP6 3 58 10 20 MSP6 4 78 20 40 Figure 5 Minimum Maximum Stroke Maximum Stroke Minimum Stroke L Yoke Surface MANUAL OPERATION FUNCTION for MSP4 AC power supply 1...

Страница 9: ...P Mounted to a Valve Remark 1 The yellow wire must be left unconnected if the position output signal is not required Cut the exposed section of copper wire and insulate the tip of the wire Remark 2 The MSP6 is not provided with full open closed signals black 1 U V COM1 COM2 COM1 white 2 red 3 green 4 yellow 5 blue 6 gray 7 brown 8 1 to 8 Terminal No of terminal box Full open closed signals and for...

Страница 10: ...ol PCB as shown in Figure 3 Other adjustments which are paint locked are for factory use only and should be changed only by qualified M System personnel M System is not liable for any malfunction or inconvenience caused by unauthorized change of them by the user DIRECT REVERSE ACTION The actuator action is factory set to Reverse the output stem is retracted with an input signal increase and the op...

Страница 11: ...l sound No abnormal sound is heard during operation Repair or calibration Connector Leadwire The connector is firmly connected No breakdown of leadwires The insulation covers are not torn not bruised Repair or calibration Inside humidity rust No condensation No rust If there is water inside check the packing Remove water dry the case and inside parts Replace rusted parts Calibration If the packing...

Страница 12: ...pply voltage Check the power supply Fuse melted Replace the fuse ON ON Malfunction by noise Turn off the power supply and restart Low power voltage or insufficient capacity Check the power supply ON OFF Malfunction by noise Turn off the power supply and restart Low power voltage or insufficient capacity Check the power supply Unstable functioning Power voltage is low or fluctuating Check the power...

Отзывы: