background image

M2UDS2

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5101  Rev.3  P. 3 / 3

EXTERNAL VIEWS

 FRONT VIEW

 SIDE VIEW

OFF

ON

1 2 3 4

SW1

Output Function

Setting

Zero Adj.

Span Adj.

Status Indicator LED1

Status Indicator LED2

 

DIP SWITCH SETTING

Choose the output function: Proportional or inverted output, or loop test output of 0%, 50% and 100%.
Set the DIP switch to appropriate positions before turning on the power supply.  No change in the switch positions is valid 
while the power is supplied.

OUTPUT

SW1-1

SW1-2

SW1-3

SW1-4

STAT1 LED

STAT2 LED

Inverted output without the limit (*)

OFF

OFF

OFF

OFF

ON

OFF

Proportional output without the limit

ON

OFF

OFF

OFF

ON

OFF

Inverted output with the limit *

1

OFF

ON

OFF

OFF

ON

OFF

Proportional output with the limit *

1

ON

ON

OFF

OFF

ON

OFF

    0%

*2

*2

ON

OFF

OFF

ON

  50%

*2

*2

OFF

ON

Blinking

ON

100%

*2

*2

ON

ON

ON

ON

(*) Factory setting
*1. The output is limited within 0 to 100%.
*2. ON/OFF position is irrelevant.

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

13 – 14 with a multimeter.

3) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4) Output:  Check that the load resistance meets the de-

scribed specifications.

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 
following.

 

HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.

1) Turn all DIP switches to OFF positions.
2) ZERO:  Apply 100% input and adjust output to 0%.
3) SPAN:  Apply 0% input and adjust output to 100%.
4) Check ZERO adjustment again with 100% input.
5) When ZERO value is changed, repeat the above proce-

dure 2) – 4).

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 100%, 
75%, 50%, 25% and 0% input signal.  Check that the output 
signal for the respective input signal shows 0%, 25%, 50%, 
75% and 100% within accuracy described in the data sheet.  
When the output is out of tolerance, recalibrate the unit ac-
cording to the “ADJUSTMENT PROCEDURE” explained 
earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.