CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

10 – 11 with a multimeter.

3) Strain gauge:  Check the bridge resistance.  The maxi-

mum current supplied to the strain gauge is 35mA.

4) Input:  When applying maximum load, check voltage 

across the terminal 1 (+) – 2 (–) equals Exc. × Strain 

Gauge Sensitivity.

5) Output:  Check that the load resistance meets the de-

scribed specifications.

ADJUSTMENT PROCEDURE

Fine Zero Adj.

Excitation Adj.

16-position

Coarse Zero Adj.

16-position

Coarse Span Adj.

Fine Span Adj.

Auxiliary

Coarse Zero Adj.

1) Excitation Adj.:  The excitation voltage is calibrated at 

the factory, therefore will not usually require adjustment, 

except when used in combination with a strain gauge of 

sensitivity other than described on the specifications.

  In that case, adjust to the value calculated by the follow-

ing equation:

Excitation [V] = 

5 [V] × a [mV/V]

b [mV/V]

where a: Factory set sensitivity value marked on the product

     

b: User’s sensitivity value

  Adjustable range is within 2V to 10V with bridge resist-

ance of 350Ω.  When the calculated value exceeds 10V, 

adjust it to 10V.

2) Coarse Zero Adj.:  Tare adjustment.  Approx. 5% of input 

span adjusted with each increment.  Max. 80% with 16 

positions.

  Without any load, adjust the output to 0%.
3) Fine Zero Adj.:  Used for fine tare adjustment.
4) Coarse Span Adj.:  Gain adjustment.  100 – 20% of input 

span adjusted with 16 positions.

  With 100% load, adjust the output to 100%.
5) Fine Span Adj.:  Used for fine gain adjustment.
6) Coarse Zero Adj. (auxiliary):  Used when the zero can-

not be adjusted with only the coarse and fine zero adjust-

ments.

  After coarse adjustment, turn the fine zero adj. to the 

middle position and adjust the output to zero.

  When not in use, the trimmer should be turned fully 

clockwise.

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.