EM-5066 Rev.6 P. 2 / 3
INSTALLATION
Loosen the fixing screw at the front of the unit in order to
separate the body from the base socket.
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
■
DIN RAIL MOUNTING
Set the base socket so that
its DIN rail adaptor is at
the bottom. Position the
upper hook at the rear side
of base socket on the DIN
rail and push in the lower.
When removing the socket,
push down the DIN rail
adaptor utilizing a minus
screwdriver and pull.
■
WALL MOUNTING
Refer to “EXTERNAL DIMENSIONS.”
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.
■
EXTERNAL DIMENSIONS unit: mm (inch)
5
9
21.5 (.85)
70.5 (2.78)
84 (3.31)
10 (.39)
15 (.59)
6 (.23)
59 (2.32)
DIN RAIL
35mm wide
[4 (.16)]
8–M3
SCREW
72 (2.83)
23 (.91)
2–4.2x5
(.17x.20)
MTG HOLE
6 (.24) deep
114 (4.49)
• When mounting, no extra space is needed between units.
4
8
12
14 13
1
4 (.16)
■
CONNECTION DIAGRAM
5
1
8
4
+
–
–
INPUT
+
+
2-WIRE XMTR
PWR SUPPLY
MONITOR
1 – 5V DC
V
50Ω
250Ω
50Ω
8
5
+
–
INPUT
1
4
+
+
1
8
4
2-WIRE
TRANSMITTER
–
+
5
+
–
■
When Used as DC Supply
■
When Used as Square Root
Extractor
250Ω
+
–
OUTPUT
9
12
U(+)
V(–)
POWER
13
14
WIRING INSTRUCTIONS
■
SCREW TERMINAL
Torque: 0.8 N·m
■
SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm
2
(AWG 22 to 16)
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd, Nichifu Co.,ltd
6 (.24) max
3.3 (.13) max
mm (inch)