background image

M2ADS

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5088  Rev.7  P. 3 / 3

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

13 – 14 with a multimeter.

3) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4) Output:  Check that the load resistance meets the de-

scribed specifications.

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 
following.

 

HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.

1) ZERO:  Apply the input signals which should lead the 

calculated result as 0%, and adjust output to 0%.

2) SPAN:  [

K

1

 + 

K

2

 ≥ 1]  Apply the input signals which should 

lead the calculated result as 100%, and adjust output to 

100%.

 [

K

1

 + 

K

2

 < 1]  Apply the input signals which should lead 

the calculated result as [100 × (

K

1

 + 

K

2

)]%, and adjust 

output to [100 × (

K

1

 + 

K

2

)]%.

3) Check ZERO adjustment again.
4) When ZERO value is changed, repeat the above proce-

dure 1) – 3).

EQUATION

  Output = 

K

1

 × Input 1 + 

K

2

 × Input 2

    

K

1

K

2

: 0.10 to 2.00 specified when ordering

     

(0.40 ≤ 

K

1

 + 

K

2

)

     

Input 1, Input 2: 0 to 120%

     

 Forcibly limited to 0% and 120% respectively when 
the signal is out of range.

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.
[

K

1

 + 

K

2

 ≥ 1]  Apply the input signals which should lead the 

calculated result as 0%, 25%, 50%, 75% and 100%.  Check 
that the output signal for the respective input signal re-
mains within accuracy described in the data sheet.
[

K

1

 + 

K

2

 < 1]  Apply the input signals which should lead the 

calculated result as 0%, [25 × (

K

1

 + 

K

2

)]%,  [50 × (

K

1

 + 

K

2

)]%,  

[75 × (

K

1

 + 

K

2

)]% and  [100 × (

K

1

 + 

K

2

)]%.  Check that the 

output signal for the respective input signal remains within 
accuracy described in the data sheet.  When the output is 
out of tolerance, recalibrate the unit according to the “AD-
JUSTMENT PROCEDURE” explained earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

Отзывы: