BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Lightning surge protector ...................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTALLATION / INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, and basic main-
tenance procedure.

LIMITATION APPLICABLE TO M-RESTER

The M-RESTER will protect electronics equipment from 
damage caused by lightning by absorbing most of the 
surge voltages.
However, M-RESTER may not be effective against cer-
tain extremely high voltages caused by a direct or almost 
direct hit by lightning.
M-RESTER must be installed according to this installa-
tion / instruction manual.

GENERALS

 

FUNCTION & FEATURES

Designed for installation where AC power enters the con-
trol panel for relatively large power consuming equipment 
such as large instrumentation panels, computer systems or 
telemetering systems in central control rooms or operation 
centers

 

SPECIFICATIONS

BETWEEN LINES

LINE TO GND

MH-1201  MH-2201/2203

Discharge voltage 
(p-p)

190V min. 380V min.

410V min.

Max. surge voltage* 350V max. 700V max.

700V max.

Leakage current

≤1A including relay coil

current at rated voltage

≤1mA

 @150V DC

(MH-1201)

@300V DC

(MH-2201/2203)

Response time

≤0.1 µsec

Discharge current

 10000A (8 / 20 µsec.)

Max. load current

 200A

Voltage drop

≤2V (50/60 Hz)

Rated line voltage

100V/110V/120V AC (MH-1201)

200V/220V/240V AC (MH-2201/2203)

*The maximum voltage that could pass through M-RESTER. 
Protected equipment must be able to withstand this voltage 
for a very short time period.

POINTS OF CAUTION

 

ENVIRONMENT

• When heavy dust or metal particles are present in the at-

mosphere, install M-RESTER inside proper housing and 
ventilate it.

• Do not install the M-RESTER where it is subjected to 

continuous vibration. Do not apply physical impact to the 
M-RESTER.

• Environmental temperature must be within -5 to +55°C 

with a relative humidity within 30 to 90% RH in order to 
ensure adequate life span and operation.

 

DIELECTRIC STRENGTH TEST

• The MH starts discharging at 410V or more voltage ap-

plied across power supply terminals and metallic hous-
ing. DO NOT conduct a dielectric strength test with the 
MH connected to a power source.

• For confirming insulation of the unit, conduct the dielec-

tric strength test WITH ALL WIRES REMOVED, or con-
duct an insulation resistance test (@250V DC).

 

RATED CURRENT

• Be sure that the rated current of protected equipment 

does not exceed the maximum load current specification 
of the M-RESTER.

• Be sure to install a breaker which matches the current 

rating at the power source side of the M-RESTER.

 

AND ....

We recommend that you keep spare M-RESTERs so that 
you can replace them when necessary.

COMPONENT IDENTIFICATION

Body

Power Pilot Lamp

Grommet with Film

Nameplate

LIGHTNING SURGE PROTECTOR FOR POWER SUPPLY USE

(200A)

MODEL

MH-1201

MH-2201

MH-2203

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8181  Rev.6  P. 1 / 4

INSTRUCTION MANUAL