MAINTENANCE

Check M-RESTER periodically. Many cases of lightning are 
ignored, and even lightning at a far distance often causes 
inductive surges.  We recommend that you check your M-
RESTER about twice a year, before and after the rainy sea-
son. Check whenever you experience a strong lightning oc-
currence.  Checking procedure is explained in the following:

 

CHECKING

WIRING

• Make sure that wiring is done as instructed in the con-

nection diagram.

• Make sure that the Ground terminal (3) is connected to 

the metallic housing of protected equipment.

• Make sure that the Ground terminal (3) is grounded to 

earth.

 

DISCHARGE FUNCTION

Remove all the wires connected to the M-RESTER and test 
its discharge capability as follows:

• Apply 150V DC across the terminals (1) – (7) and (2) – (8) 

with a resistor of approx. 10kW in serial. Measure leak-
age current. (

1mA standard)  Check also that the power 

indicator LED is ON.

• Then apply 250V DC and check that discharging occurs. 

(

2mA standard)

• Apply 300V DC across the following terminals and meas-

ure leakage current. (

1mA standard)

     Terminals (1) – (3), (7) – (3), (2) – (3), (8) – (3)

• Then apply 500V DC and check that discharging occurs. 

(

2mA standard)

• If DC power source is not available, check resistance 

across the following terminals on the high resistance 
range of multimeter (infinite standard).

     

Terminals (1) – (7), (1) – (3), (7) – (3), (2) – (8), (2) – (3), (8) – (3)

• Check that discharging occurs across the same terminals 

with a 500V DC megger. (Indicator of the megger reaches 
over-scale.)

• If any of the above tests shows negative, replace the whole 

M-RESTER unit.