TERMINAL CONNECTION

Connect the unit as in the diagram below.
Be sure to cross-wire between the Ground terminal (G) and that of the protected equipment.  When the surge protector is 
connected with a device which has no ground terminal such like M-System’s (See figure below), ground the M-Rester Ground 
terminal (G) only.

Protected Device

MDP-LWA

G

1
3

A
C

2

SHLD

G

B

NET

A, B

Grounding

Cross wiring

*

3

*

2

*

1

*

1. Be sure to use twisted-pair cables.

*

2. No polarity.

*

3. With shielded twisted-pair cables, connect the shield to the surge protector’s  B  terminal. 

      

Follow instructions provided with the protected device whether  2  terminal should be 

      connected or not.  However, if the shield terminal of the protected device is not isolated 

      from NET A / B, DO NOT connect  2  terminal to the protected device.

M-RESTER

PROTECTED

EQUIPMENT

G

G

CROSSOVER WIRE

GROUNDING

(100 ohms or less)

A crossover wire between M-RESTER ground and the ground or 

metallic housing of the equipment is required for protection.

If the protected equipment has no ground terminal, ground the 

M-RESTER only.

 GROUNDING

 NETWORK CONFIGURATION

Protected

Devices

(Nodes)

MDP-LWA

G

G

G

MDP-LWA

G

G

G

Protected

Devices

(Nodes)

• The MDP-LWA is applicable to networks which consist only of FTT-10A.

  Not applicable to the ones connected to Link Power network.

• The maximum number of nodes connectable to the network segment is reduced by one

  when one unit of MDP-LWA is added.

• When the distance between nodes are relatively long (e.g. grouped and separated by cabinets),

  install the MDP-LWA by each group of devices.  Insert the MDP-LWA at the surge side of the network.

• For detailed information on the network, refer to LONWORKS FTT-10A Free Topology Transceiver 

  User’s Guide provided by Echelon.

Crossover Wire

Crossover Wire

Grounding

Panel / Cabinet

Protected Side

Surge Side

Network Cable

Network Cable

Panel / Cabinet

Protected Side

Surge Side

Network Cable