EM-8234 Rev.

LIGHTNING SURGE PROTECTOR FOR 

L

ON

W

ORKS

 

(FTT-10A)

MODEL

MDP-LWA

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If  you  have  any  problems  or  questions  with  the  product, 
please contact M-System’s Sales Office or representatives.

 PACKAGE INCLUDES:

  Surge protector ............................................................. (1)

 MODEL NO.

Confirm  Model  No.  marking  on  the  product  to  be  exactly 
what you ordered.

 INSTRUCTION MANUAL

This  manual  describes  necessary  points  of  caution  when 
you use this product, including installation, connection and 
basic maintenance procedures.

LIMITATION APPLICABLE TO M-RESTER

The  M-Rester  will  protect  electronics  equipment  from 
damage  caused  by  lightning  by  absorbing  most  of  the 
surge voltages.
However, M-Rester may not be effective against certain 
extremely high voltages caused by a direct or almost di-
rect hit by lightning.
M-Rester must be installed according to this installation 
/ instruction manual.

GENERAL

 FUNCTION & FEATURES

• Designed specifically for L

ON

W

ORKS

 network

• No interruption of transmission signal by unplugging the 

head element module

 SPECIFICATIONS

POINTS OF CAUTION

 ENVIRONMENT

• When heavy dust or metal particles are present in the air, 

install the surge protector inside proper housing with suf-
ficient ventilation.

• Do not install the surge protector where it is subjected to 

continuous vibration.  Do not subject the unit to physical 
impact.

• Environmental temperature must be within -5 to +55°C     

(23 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 NETWORK SPECIFICATIONS

• The  MDP-LWA  is  applicable  to  networks  which  consist 

only of FTT-10A.  Not applicable to the ones connected to 
Link Power network.

• For  detailed  information  on  the  network,  refer  to  L

ON-

W

ORKS

 FTT-10A Free Topology Transceiver User’s Guide 

provided by Echelon.

 DIELECTRIC STRENGTH TEST

• Loosen the screw located at the left-center of the element 

and  remove  the  element  module  from  the  base  before 
conducting  a  dielectric  strength  testing.    Otherwise  the 
element will start discharging at a voltage exceeding the 
max. continuous operating voltage (Uc), which can cause 
insulation failure of the module.

  Be sure to return the element and fasten securely after 

the test.

 AND ....

• We  recommend  that  you  keep  spare  surge  protectors  so 

that you can replace them when necessary.

• Lightning surge can enter not only through signal lines 

but also through power supply lines.  We recommend that 
you also use the surge protectors for power line for suf-
ficient protection.

COMPONENT IDENTIFICATION

Ground Terminal (G)
(used as mounting bracket)

Base

Element is secured to Base 

with screw when M-RESTER is 

shipped from Factory.

M•RESTER

MADE IN JAPAN N1430

B

Lot.N

O

MODEL

Head Element

Specifications

 

LINE TO 

LINE TO 

SHLD TO 

 

LINE 

EARTH 

EARTH

Max. continuous 

±1.5V min  ±100V min  ±160V min 

operating voltage (Uc)
Voltage protection level  ±40V max  ±350V max  ±650V max 

(Up) @2kV (1kA)
Leakage current 

≤0.15mA 

≤20µA 

≤±20µA 

 

@±1.5V 

@±100V 

@±160V

Capacitance @1 MHz  ≤200 pF 

≤200 pF 

≤30 pF

Response time 

≤4 nsec. 

≤20 nsec. 

≤20 nsec.

Max. discharge current  

5000A (8 / 20 µs) 

 

(Imax) 
Nominal current (I

N

100mA

Internal series resistance 

≤3.3Ω including return

Max. line voltage 

±1.5V

Input attenuation 

-1 dB max. @DC...100 kHz, Z

0

 = 50Ω