INSTALLATION

Set the unit so that its DIN rail adapter is at the bottom. 
Hung the upper hook at the rear side of unit on the DIN rail 
and push in the lower.  When removing the unit, push down 
the DIN rail adapter utilizing screwdriver (–) and pull.

DIN Rail

35mm wide

Spring Loaded

DIN Rail Adaptor

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.
Be sure to cross-wire between the ground terminal (No. 5 or 10) and that of the protected equipment.
When the M-RESTER is connected with a device which has no ground terminal such like M-System's (See figure to the right), 
ground the M-Rester ground terminal (No. 5 or 10) only.

M-RESTER

6

7

1

2

M-RESTER

5

1

2

6

7

8

3

3

8

(PROTECTED EQUIPMENT)

9

4

4

9

STRAIN GAUGE

XMTR

SHIELDED WIRE

+

+

G

+

OUTPUT

V

U

POWER

EXC.

INPUT

10

5

G

STRAIN GAUGE

EXC.

OUTPUT

 

GROUNDING

M-RESTER

PROTECTED

EQUIPMENT

G

G

CROSSOVER WIRE

GROUNDING

(100 ohms or less)

A crossover wire between M-RESTER ground and ground or metallic 

housing of equipment is required for protection.

If the protected equipment has no ground terminal, ground the 

M-RESTER only.

MDK-LC