WIRING INSTRUCTIONS
Applicable wire size range for euro type connector terminal
of communication is as shown below.
• Applicable wire size
Solid:
0.2 to 2.5 mm
2
(0.55 to 1.75 dia.)
Stranded: 0.2 to 2.5 mm
2
Tinning wire ends may cause contact failure
and therefore is not recommended.
Ferruled: 0.2 to 1.5 mm
2
(0.55 to 1.35 dia.)
The following Phoenix Contact terminals are recommended:
AI 0.25-8YE 0.2 to 0.25 mm
2
AI 0.34-8TQ 0.25 to 0.34 mm
2
AI 0.5-8WH 0.34 to 0.5 mm
2
AI 0.75-8GY 0.5 to 0.75 mm
2
AI 1.0-8RD 0.75 to 1.0 mm
2
AI 1.5-8BK 1.0 to 1.5 mm
2
• Expose wire conductors by 8 mm (0.31”).
8 mm
8 mm
4 mm dia.
max.
4 mm dia.
max.
Wire exposure
Recommended
ferruled wire
MAINTENANCE
Check surge protectors periodically. Many cases of light-
ning are ignored, and even lightning at a far distance often
causes inductive surges.
We recommend that you check your surge protector about
twice a year, before and after the rainy season. Check
whenever you experience a strong lightning occurrence.
Checking procedure is explained in the following:
■
CHECKING
1. WIRING
• Make sure that wiring is done as instructed in the con-
nection diagram.
2. DISCHARGE ELEMENT
Approximate checking can be conducted as following.
• Shortcircuit test
1) Remove all cables connected to the MDCAT-SPE.
2) Remove also the shortcircuit bar.
3) Check resistance across the following terminals on the
high resistance range of multimeter and confirm no con-
duction. (The meter will indicate the same value as it
will show when these terminals are open.)
(1)-G, (2)-G, (3)-G
4) Then, apply ±60V DC across the following terminals and
measure leakage current to show ≤ 5µA. If a voltage gen-
erator is not available, check resistance with a multim-
eter and confirm no conduction. (Use of a voltage genera-
tor is strongly recommended.)
• Discharging test
1) Check that discharging occurs across the following termi-
nals with a ±500V DC 1000 MΩ insulation tester.
(The tester shows ≤ 20MΩ.)
(1)-G, (2)-G, (3)-G