 WIRING INSTRUCTIONS

Applicable wire size range for euro type connector terminal 
of communication is as shown below.
• Applicable wire size
  Solid:  

0.2 to 2.5 mm

2

 (0.55 to 1.75 dia.)

  Stranded:  0.2 to 2.5 mm

2

   

 

Tinning wire ends may cause contact failure  

 

 

 

and therefore is not recommended.

  Ferruled:  0.2 to 1.5 mm

2

 (0.55 to 1.35 dia.)

The following Phoenix Contact terminals are recommended:
   

 

AI 0.25-8YE  0.2 to 0.25 mm

2

   

 

AI 0.34-8TQ  0.25 to 0.34 mm

2

   

 

AI 0.5-8WH  0.34 to 0.5 mm

2

   

 

AI 0.75-8GY  0.5 to 0.75 mm

2

   

 

AI 1.0-8RD  0.75 to 1.0 mm

2

   

 

AI 1.5-8BK  1.0 to 1.5 mm

2

• Expose wire conductors by 8 mm (0.31”).

8 mm

8 mm

4 mm dia.

max.

4 mm dia.

max.

Wire exposure

Recommended
ferruled wire

MAINTENANCE

Check surge protectors periodically.  Many cases of light-
ning are ignored, and even lightning at a far distance often 
causes inductive surges.
We recommend that you check your surge protector about 
twice a year, before and after the rainy season.  Check 
whenever you experience a strong lightning occurrence.
Checking procedure is explained in the following:

 

CHECKING

1. WIRING

• Make sure that wiring is done as instructed in the con-

nection diagram.

2. DISCHARGE ELEMENT

Approximate checking can be conducted as following.

• Shortcircuit test

1) Remove all cables connected to the MDCAT-SPE.
2) Remove also the shortcircuit bar.
3) Check resistance across the following terminals on the 

high resistance range of multimeter and confirm no con-

duction.  (The meter will indicate the same value as it 

will show when these terminals are open.)

  (1)-G, (2)-G, (3)-G
4) Then, apply ±60V DC across the following terminals and 

measure leakage current to show ≤ 5µA.  If a voltage gen-

erator is not available, check resistance with a multim-

eter and confirm no conduction.  (Use of a voltage genera-

tor is strongly recommended.)

• Discharging test

1) Check that discharging occurs across the following termi-

nals with a ±500V DC 1000 MΩ insulation tester.  

  (The tester shows ≤ 20MΩ.)
  (1)-G, (2)-G, (3)-G