MDCAT
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-8139 Rev.4 P. 2 / 4
GENERAL
■
FUNCTION & FEATURES
• Designed specifically for Ethernet network
• Conforms with 1000 Base-T, PoE and PoE Plus
• LAN cable’s shield wire can be floating or grounding by a shortcircuit bar
• DIN rail mounting
■
SPECIFICATIONS
LINE TO LINE (pair)
LINE
TO
LINE (PoE)
LINE
TO
EARTH
MDCAT-5E
MDCAT-6
Max. continuous operating voltage (Uc)
±6V
±3.3V
±58V
±150V
Voltage protection level (Up)
±15V @2kV
±10V @2kV
±100V @2kV
±600V @4kV
Leakage current @Uc
25µA
5µA
25µA
5µA
Response time
≤ 4 nsec.
≤ 4 nsec.
≤ 4 nsec.
≤ 20 nsec.
Max. discharge current (Imax)
100A
100A
100A
10kA
Nominal current (I
N
)
1A
Series resistance
Approx. 0Ω
Transmission performance: TIA/EIA-568-B.2
CAT5e
(MDCAT-5E)
CAT6
(MDCAT-6)
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■
EXTERNAL DIMENSIONS unit: mm (inch)
90 (3.54)
3.5 (.14)
[3 (.12)]
40 (1.57)
MODULAR JACK,
SURGE SIDE
MODULAR JACK,
PROTECTED SIDE
DIN RAIL
(35mm wide)
• When mounting, no extra space is needed between units.
SHORTCIRCUIT BAR
SHIELD TERMINAL (SHLD)
EARTH TERMINAL (G)
35 (1.38)
38 (1.50)
2-M3 SCREW
6 (.24) [4.5 (.18) deep]
11
(.43)
50 (1.97)
4.2 (.17)
35 (1.38)
7.3 (.29)
■