background image

MD7ST

EM-8057  Rev.4  P. 4 / 4

 

CONNECTION DIAGRAM

• 

Specify ‘Loop disconnect fuse’ type when multiple transmitters are connected to single power bus.

• 

Loop disconnect fuse is used to separate a transmitter loop from the power bus when it fails in the shortcircuit mode.

5

2

8

4

1

(SHLD)

DIN RAIL

DIN RAIL

ADAPTOR

Current Loop Supply

4 – 20mA

Transmitter

Field-mount

Surge Protector

(model: MD6x)

+

+

FG

Protected Side

Crossover Wire

Surge Side

*

1. Oxide film on the surface of an aluminium rail may lower the electric conductivity between this module and the ground.

Use a steel or copper rail.

*

2. Be sure to ground the DIN rail.  Recommended grounding resistance ≤100

Ω

*

3. Cross-wire between the DIN rail and the metal housing of the protected device to equalize the earth potential.

Ground only the surge protector when the protected device has no ground terminal.

*

4. Shield wiring method is an example.  Proceed according to the system requirements.

*

4

*

2

*

1

*

3

WIRING INSTRUCTIONS

 

EURO TERMINAL 

Torque: 0.3 N·m
Applicable wire size: 0.2 – 2.5 mm

2

Stripped length: 8 mm

MAINTENANCE

Check surge protectors periodically.  Many cases of light-
ning are ignored, and even lightning at a far distance often 
causes inductive surges.
We recommend that you check your surge protector about 
twice a year, before and after the rainy season.  Check 
whenever you experience a strong lightning occurrence.
Checking procedure is explained in the following:

 

CHECKING

WIRING

1) Make sure that wiring is done as instructed in the con-

nection diagram.

2) Make sure that the DIN rail is connected to the metal

enclosure of protected device.

3) Make sure that the surge protector is securely attached

to the DIN rail, and that the rail is grounded to earth.

 

DISCHARGE ELEMENT

1) Remove all wiring connected to the surge protector when

you test the module.

2) Check resistance across the terminals indicated in Table

2 on the high resistance range of multimeter and confirm

no conduction.  The tester should show 10 MΩ or greater.

3) Confirm conduction across the same terminals with a 500 

V DC 1000 MΩ insulation tester.  The tester should show

20 MΩ or less.
With loop disconnect fuse option, confirm conduction

across the following terminals on the high resistance

range of multimeter.  The tester should show 15 Ω or less.
  1 – 4, 2 – 5
Polarity of the insulation tester does not matter.

4) If any of the above tests shows negative, replace the

surge protector.

Table 2.

TERM.

          MODEL

MD7ST-xFF MD7ST-xFG MD7ST-xGF MD7ST-xGG

4 – 5

Yes

Yes

Yes

Yes

4 – 8

No

Yes

Yes

Yes

5 – 8

No

Yes

Yes

Yes

8 – 5

No

No

Yes

Yes

5 – DIN rail

Yes

Yes

No

Yes

8 – DIN rail

Yes

No

Yes

No

Note 1:  Apply (+) voltage of the multimeter to the terminal 

number indicated on the left side.

Note 2: Polarity does not matter for the insulation tester.