TERMINAL CONNECTION
Connect the unit as in the diagram below.
Be sure to ground the DIN rail on which the unit is mounted.
This unit, designed to connect shield wires and cross wires of the protected devices to a DIN rail, is NOT used to ground the
DIN rail.
■
EXTERNAL DIMENSIONS unit: mm (inch)
8
6
5
4
1
2
3
7
4
1
5
2
6
3
8
7
95 (3.74)
7
(.28)
98 (3.86)
[1.5 (.06)]
8–M3 EURO
TERMINAL
DIN RAIL
(35 mm wide)
DIN RAIL
ADAPTOR
WIRE INSERTION ANGLE: approx. 20°
57 (2.24)
1.9 (.07)
■
CONNECTION DIAGRAM
2
5
3
6
8
7
1
4
DIN RAIL ADAPTOR
(for grounding)
DIN RAIL
Grounding
DO NOT connect to unused terminals.
*
1. Oxide coating of an aluminium rail may lower the electric conductivity
between this module and the ground. Use a steel or copper rail.
*
2. Be sure to ground the DIN rail.
Recommended grounding resistance ≤100
Ω
*
2
*
1
WIRING INSTRUCTIONS
■
EURO TERMINAL
Torque: 0.3 N·m
Applicable wire size: 0.2 – 2.5 mm
2
Stripped length: 8 mm
■
CAUTION WHEN WIRING
Hold the module steady at the front when you
tighten/loosen screw terminals.