INSTALLATION DIAGRAM for CENELEC INTRINSICALLY SAFE MODEL

NOTES
1.   The parameters of AA and IS apparatus protected by the MD7FB shall comply with 
       the following conditions.

         

Uo 

 Ui

1

, Ui

2

 or Ui

equipment

whichever is smallest. 

         

Io 

 

Ii

1

, Ii

2

 or Ii

equipment

whichever is smallest.

         

Po 

 

Pi

1

, Pi

2

 or Pi

equipment

,

 whichever is smallest.

         

Co 

 Ci

1

+ Ci

2

 + Ci

equipment

 + Cc

        

 Lo 

 Li

1

 + Li

2

 + Li

equipment

 + Lc

       When multi-drop wiring is used, Ci

2, 

Ci

equipment

Li

and Li

equipment

  

must be the total capacitance and

       inductance of all the apparatus connected to the bus line.

2.    Either one of the two MD7FB may be a different lightning surge protector certified by a notified body 
       under ATEX directive 2014/34/EU.

3.    The associated apparatus and the IS apparatus must be certified by a notified body under ATEX
       directive 2014/34/EU.
       In case of isolated associated apparatus, the earth is not required.

4.   When shield wiring is used, it must be connected  to earth in the non-hazardous location.

5.   Shield wiring method depends on the system requirement.

Maximum Input Power Pi

17.5 V

5.4 W

Maximum Input Inductance Li

Maximum Input Capacitance Ci

Maximum Input Current Ii

Maximum Input Voltage Ui

Electrical Data

Linear Barrier FISCO Supply

any

5 nF

μ

H

32 V

400 mA

5 nF

μ

H

see right

Maximum Input Power Pi for Linear Barrier:  
  For T4 and Ta=-25 to 40°C: 1.3W
  For T4 and Ta=-25 to 60°C: 1.2W
  For T4 and Ta=-25 to 80°C: 1.0W
  For T5 and Ta=-25 to 40°C: 1.0W

Non-Hazardous Location

Hazardous Location

Zone 0, 1 and 2

IS Apparatus 

*

1,3

DIN rail

4

5

8

Ui

2

Ii

2

Pi

2

Ci

2

Li

2

Cable Capacitance: Cc
Cable Inductance: Lc

*

4

Ui

equipment

Ii

equipment

Pi

equipment

Ci

equipment

Li

equipment

*

5

+

-

+

-

Associated
Apparatus 

*

1,3

Uo
Io
Po
Co
Lo

4

5

DIN rail

Ui

1

Ii

1

Pi

1

Ci

1

Li

1

MD7FB

*

5

1

2

7

+

3

-

SHLD

6

6

8

Bus Line

1

2

3

MD7FB

*

2

*

2