M-system MAT2 Series Скачать руководство пользователя страница 5

MAT2

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8149  Rev.6  P. 5 / 6

WIRING

 

LEADWIRES

Conductor cross-section area: 5.5 mm

2

 minimum for both 

the power and the ground lines.  However, a local industrial 
standard requirement for wiring should take precedence.

 

SOLDERLESS TERMINAL

Applicable ring tongue terminal without insulation sleeve 
is as indicated below.  Spade tongue terminal must conform 
with the ring type size.
In order to ensure IP20 protection (IEC 60529) with a sol-
derless terminal, cover the terminal with a insulation cap  
to prevent direct touching by a hand.

F

d : M5 use
B ≤ 13.0 mm
F ≥ 7.0 mm
(F ≥ 8.2 mm for sharing terminals)
T ≤ 1.8 mm

• Applicable Solderless Terminal Size

diameter d

B

T

 

TORQUE

Tighten the screw terminals securely.  Maximum allowable 
torque is of 2.5 N·m.

 

WIRE LENGTH

Keep the wire length to the minimum for both the power 
source side and the ground side.  An example with single-
phase/two-wire configuration is shown below.  The wire 
length between the branch point and the ground ( ‘a’ in the 
figure) should ideally be less than 0.5 meters.  Extra long 
wires should not be bundled in coils, but be cut to the mini-
mum required length.

 

PROTECTING LOW-VOLTAGE EQUIPMENT

The MAT2, one-port surge protector, is most suitable to 
protect electric devices such as isolation transformers, heat-
ers, electromagnetic contactors, motors.  On the other hand, 
combination type surge protectors incorporating serial im-
pedance (M-System model examples: MAX, MMA, MAH) 
are suitable to protect low-voltage electric devices such as 
computers, measuring instruments, transmission devices.
However, when the distance between the distribution 
switchboard and the protected device ( ‘b’ in the figure) 
is longer than 20 or 30 meters, the reactance of the wires 
would function as serial impedance in the combination type 
surge protectors.  
In this case, the overall protection performance should be 
augmented by one-port surge protectors installed inside the 
switchboard and next to the protected device, protected de-
vice side cross-wired to the ground.

• Single-Phase/2-wire connection

Protected 

Device

Cross-wiring

Distribution Switchboard

Power Source

a

b

G

U

V

PE

(N)

Circuit breaker 

2

1

PE

N

3

MAT2

PE

Circuit breaker

2

1

PE

N

3

MAT2

GROUNDING

 

COMMON GROUNDING WITH CROSS-OVER WIRE

Basically a common grounding with cross-wiring between 
the MAT2 and the protected device is recommended for ade-
quate protection.  Grounding resistance should be less than 
100 ohms.  If the protected device has no ground terminal, 
ground only the MAT2.
The ground point should be close to the MAT2 side as shown 
below.

• Single-Phase/2-wire connection

Cross-wiring

PE

Protected 

Device

G

U

V

(N)

PE

Circuit breaker

2

1

PE

N

3

MAT2

 

INDEPENDENT GROUNDING

The MAT2 installed inside a distribution switchboard is of-
ten located far from the protected device, thus an independ-
ent grounding is needed.  In such cases, keep the grounding 
resistance as low as possible (several ohms), or add another 
MAT2 for local protection next to the protected device.

ALARM OUTPUT

Optional SPDT relay output is available to alert when the 
thermal breaker has separated the discharge element from 
the power supply circuit.
If the alarm output should be transmitted remotely via out-
door cables, a surge protector for signal line is required.
Choose a circuit breaker with an alarm output.  Configure a 
logical addition sequence so that the alarm trips when both 
or either of the MAT2 or the breaker alarm trips.

 

RELAY SPECIFICATIONS

Alarm output:  

The SPDT relay trips when the thermal 
breaker operates and/or power source shut-
down.

Rated load:   250V AC @1A (resistive load)
     

 

 

24V DC @1A (resistive load)

 

CONNECTION

Terminal: Tension clamp
Applicable wire size: 0.13 to 1.5 mm

2

Stripped length: 8 mm

CHECKING

 

WIRING

• Make sure that wiring is done as instructed in the con-

nection diagram.

• Make sure that the Ground terminal (G) is connected to 

the metallic housing of protected equipment.

• Make sure that the Ground terminal (G) is grounded to 

earth.

Отзывы: