![M-system M8MS1 Скачать руководство пользователя страница 2](http://html.mh-extra.com/html/m-system/m8ms1/m8ms1_instruction-manual_683680002.webp)
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■
EXTERNAL DIMENSIONS unit: mm (inch)
I/O PINS
17.5 (.69)
48 (1.89)
75 (2.95)
83 (3.27)
■
CONNECTION DIAGRAM
+
–
Installation Base
OUTPUT 1
6
7
8
9
10
11
+
–
+
–
OUTPUT 2
POWER
+
–
1
2
3
2
1
POTENTIOMETER
max.
min.
4
A
B
C
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input: Check the power input voltage.
3) Input: Check voltage across the terminal B (+) – C (–)
with a voltmeter to show 0V at 0% potentiometer input
and the same voltage as that across A (+) – C (–) at 100%
input.
4) Output: Check that the load resistance meets the de-
scribed specifications.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory with the total resist-
ance input, therefore you do not need any calibration if you
use the potentiometer’s total resistance.
When you do not use the total resistance or in case of regu-
lar calibration, adjust the output as explained in the fol-
lowing.
■
HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
(Output 1 and Output 2 are linked.)
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
MAINTENANCE
Regular calibration procedure is explained below:
■
CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.
M8MS1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5376 P. 2 / 2