M6NPP
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-7919 Rev.4 P. 3 / 3
■
CONNECTION DIAGRAM
1
3
2
5
6
–
+
+
+
+
–
–
OUTPUT
POWER
INPUT
SENSOR EXCITATION
CONNECTOR
POWER
7
8
■
Mechanical Contact or Open Collector
Input Connection Examples
■
Voltage Pulse
+12V
■
Open Collector
Output Connection Examples
+
–
5
6
+
–
■
Voltage Pulse
+
–
5
6
+
–
+
+
–
–
PWR
+
+
–
–
PWR
+
–
1
2
+ 3
+
–
1
2
+ 3
■
2-Wire Current Pulse
•
External DC Supply
+
2-WIRE
PICK-UP
1
2
3
–
+
2-WIRE
PICK-UP
1
2
3
–
DC SUPPLY
+
–
+
•
Built-in Excitation
200 Ω
+12V
5 kΩ
+12V
200 Ω
+12V
WIRING INSTRUCTIONS
■
SCREW TERMINAL
Torque: 0.5 N·m
■
SOLDERLESS TERMINAL unit: mm (inch)
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable.
Solderless terminals with insulation sleeve do not fit.
Applicable wire size: 0.2 – 2.5 mm
2
3.2 (.13) dia.
4 min.
(.16)
5.8 max.
(.23)
5.5 max.
(.22)
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
7 – 8 with a multimeter.
3) Input: Check that the input frequency is 30 Hz or less
for relay contact, 100 kHz or less for other types of input.
Check also that input pulse is 10 msec. or wider for relay
contact, 5 µsec. or wider for other types of input.
4) Output: Check that the load resistance meets the de-
scribed specifications as shown below.
OUTPUT
LOAD REQUIREMENTS
Open collector
50 V DC @ 100 mA max.
Voltage pulse
1.0 kΩ min. for 5 V
2.4 kΩ min. for 12 V
4.8 kΩ min. for 24 V
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.