 CONNECTION DIAGRAM

 WIRING INSTRUCTIONS

  • Applicable wire size
   

Solid:  

0.2 to 2.5 mm

2

 (0.55 to 1.75 dia.)

   

Stranded:  0.2 to 2.5 mm

2

 (Tinning wire ends may 

   

 

 

cause contact failure and therefore is not 

   

 

 

recommended.)

   

Ferruled:  0.2 to 1.5 mm

2

 (0.55 to 1.35 dia.)

  • Expose wire conductors by 8 mm (0.31”).

TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.

 EXTERNAL DIMENSIONS  unit: mm (inch)

94 (3.70)

5.9 (.23)

DIN RAIL HOOK

102 (4.02)

[0.5 (.02)]

8–M3
EURO TERMINAL

DIN RAIL
35mm wide

5

6

7

8

1

2

3

4

• When mounting, no extra space is needed between units.

WIRE INSERTION ANGLE: approx. 7°

SCREWDRIVER
INSERTION ANGLE
: approx. 40°

7

8

2

4

3

NC

NO

COM

A

B

A

B

B

6

1

5

RTD

2-wire

3-wire

CONFIGURATOR

JACK

+

OUTPUT

POWER

8 mm

8 mm

3.7 mm dia.

max.

3.7 mm dia.

max.

Wire exposure

Recommended
ferruled wire

How to Connect Wires

Insert a wire.  Confirm that the wire tip hits the bottom and 
tighten the screw with a screwdriver.
Confirm that the wire’s insulation tube is not caught in the 
terminal.

Screwdriver

Wire

Screwdriver

Wire

8 mm

6 mm

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Содержание M6DXAR

Страница 1: ...ELATED PRODUCTS PC configurator software model M6CFG Downloadable at M System s web site A dedicated cable is required to connect the module to the PC Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types GENERAL SPECIFICATIONS Connection Input and output Euro terminal torque 0 3 N m Power input Via the Installation Base model M6...

Страница 2: ...to 55 C 4 to 131 F Operating humidity 30 to 90 RH non condensing Mounting Installation Base model M6DBS or DIN rail Weight 65 g 2 3 oz PERFORMANCE in percentage of span Setpoint accuracy trip point accuracy Pt and JPt Whichever greater 0 1 of input range or 0 15 C Cu10 1 C Temp coefficient 0 01 C 0 006 F of max span Response time 1 sec 0 100 at 90 setpoint Burnout response time 1 sec Line voltage ...

Страница 3: ... RAIL HOOK 102 4 02 0 5 02 8 M3 EURO TERMINAL DIN RAIL 35mm wide 5 6 7 8 1 2 3 4 When mounting no extra space is needed between units WIRE INSERTION ANGLE approx 7 SCREWDRIVER INSERTION ANGLE approx 40 Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www sentronic com Produkte Support und Service SENTRONICAG ...

Страница 4: ...oad Coil Diode Varistor or CR Circuit Low Drift Amplifier STATUS LED ALARM MONITOR LED POWER Digital Computation Ry JACK CONFIGURATOR RTD 2 wire 3 wire OUTPUT CONNECTOR POWER POWER LED Specifications are subject to change without notice Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www sentronic com Produkte Support und Service SENTRONICAG ...

Страница 5: ...hat appropriate clearance and creepage distances are maintained to con form to CE requirements Failure to observe these re quirements may invalidate the CE conformance POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 24V DC rating 24V 10 approx 0 5W GENERAL PRECAUTIONS Before you remove the unit or mount i...

Страница 6: ...DIN rail adaptor using a minus screw driver B Pull out the lower part of the unit C Remove the upper part from the DIN rail DIN Rail A B DIN Rail Adaptor A B C COMPONENT IDENTIFICATION Body Front Cover DIN Rail Adaptor Spec Marking Status Indicator LED Configurator Jack Power LED Alarm Monitor LED FRONT VIEW with the cover open Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 ...

Страница 7: ...L DIN RAIL 35mm wide 5 6 7 8 1 2 3 4 When mounting no extra space is needed between units WIRE INSERTION ANGLE approx 7 SCREWDRIVER INSERTION ANGLE approx 40 7 8 2 4 3 NC NO COM A B A B B 6 1 5 RTD 2 wire 3 wire CONFIGURATOR JACK OUTPUT POWER 8 mm 8 mm 3 7 mm dia max 3 7 mm dia max Wire exposure Recommended ferruled wire How to Connect Wires Insert a wire Confirm that the wire tip hits the bottom ...

Страница 8: ...ined below CALIBRATION Warm up the unit for at least 10 minutes H Setpoint Increase the input signal from a value lower than the set point and check that the relay trips at the H setpoint within the setpoint accuracy described in the data sheet L Setpoint Decrease the input signal from a value higher than the set point and check that the relay trips at the L setpoint within the setpoint accuracy d...

Отзывы: