TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the 
connection diagram on the front of the unit.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

94 (3.70)

3 (.12)

25 (.98)

41 (1.61)

[3.3 (.13)]

• When mounting, no extra space is needed between units.

DIN RAIL

35mm wide

8–M3.5 SCREW

7.3 (.29)

1 2

3 4

5 6

7 8

 

CONNECTION DIAGRAM

4kΩ

■ 

Mechanical Contact, Open Collector

    or Clamp-on Pulse Sensor CLSP

Input Connection Examples 

+12V

■ 

Voltage Pulse

+12V

■ 

Open Collector

Output Connection Examples 

+

5

6

+

■ 

Voltage Pulse

+

5

6

+

+

+


PWR

+

+


PWR

+

3

4

+ 1

+

3

4

+ 1

+

OUTPUT

5

6

U(+)

V(–)

POWER

7

8

+

INPUT

3

1

4

+

SENSOR EXCITATION

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.8 N·m

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

7 – 8 with a multimeter.

3) Input:  Check that the input frequency is 30 Hz or less for 

relay contact, 10 kHz or less for other types of input.

  Check also that the input pulse is of 10 msec. or wider for 

relay contact, 10 µsec. or wider for other types of input. 

4) Output:  Check that the load resistance meets the de-

scribed specifications as shown below.

OUTPUT

LOAD REQUIREMENTS

Open collector

50 V DC @ 100 mA max.

Voltage pulse

1.0 kΩ min. for 5 V
2.4 kΩ min. for 12 V
4.8 kΩ min. for 24 V

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.