background image

M5DY

P. 2 / 2

EM-2476 Rev.6

M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship 
during the 36-month period following the date that such product was originally purchased if such product has been used under 
normal operating conditions and properly maintained, M-System’s sole liability, and purchaser’s exclusive remedies, under this 
warranty are, at M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is 
defective under the terms of this warranty.  To submit a claim under this warranty, the purchaser must return, at its expense, the 
defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, 
EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICU-
LAR PURPOSE.  M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES 
OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-
8510, E-mail: [email protected]

TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the con-
nection diagram on the front of the unit.

 EXTERNAL DIMENSIONS  unit: mm (inch)

 CONNECTION DIAGRAM

94 (3.70)

3 (.12)

25 (.98)

41 (1.61)

[3.3 (.13)]

• When mounting, no extra space is needed between units.

35.4 (1.39)

DIN RAIL

35mm wide

8–M3.5 SCREW

7.3 (.29)

1 2

3 4

5 6

7 8

+

OUTPUT

5
6

+

+

1
2

3
4

2-WIRE

TRANSMITTER

+

MONITOR

(1 – 5V DC)

V

8

7

U(+)

V(–)

POWER

2-WIRE

XMTR

+

+

INPUT

+

+

1

4

2

+

+

249.5

■ 

When Used as DC Supply

■ 

When Used as Isolator

3

1

4

2

249.5

3

CHECKING

1)  Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2)  Power input voltage:  Check voltage across the terminal 

7 – 8 with a multimeter.

3)  Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4)  Output:    Check  that  the  load  resistance  meets  the  de-

scribed specifications.

ADJUSTMENT PROCEDURE

This  unit  is  calibrated  at  the  factory  to  meet  the  ordered 
specifications,  therefore  you  usually  do  not  need  any  cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 
following.

 HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.
1)  ZERO:  Apply 0% input and adjust output to 0%.
2)  SPAN:  Apply 100% input and adjust output to 100%.
3)  Check ZERO adjustment again with 0% input.
4)  When  ZERO  value  is  changed,  repeat  the  above  proce-

dure 1) – 3).

MAINTENANCE

Regular calibration procedure is explained below:

 CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%,  75%  and  100%  input  signal.    Check  that  the  output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance,  recalibrate  the  unit  according  to  the “ADJUST-
MENT PROCEDURE” explained earlier.