M3LPA2
P. 5 / 10
EM-2657 Rev.3
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
■
POLARITY (SW3)
Table 7
POLARITY SW3-6
Bipolor OFF
Unipolor ON
When Bipolor is selected, the internal threshold level is
fixed to 0V.
■
EXCITATION SUPPLY (SW3)
Table 8
EXCITATION SW3-5
SW3-4
4V
ON
OFF
8V
OFF
ON
12V ON ON
■
PULSE SENSING (SW4)
*
2
Table 9
SENSING SW4-3
Capacitor coupled *
3
OFF
DC coupled *
4
ON
*2. DIP SW setting is required for PC configuration type.
*3. Frequency range must be 0 – 100 Hz or higher. 0 –
1
kHz or higher for sinusoidal waveform input. Frequencies
lower than 10 Hz may be out of accuracy conformance.
*4. For sinusoidal waveform input with the pulse ampli
-
tude smaller than 1V p-p, the frequency range must be 0
– 1 kHz or higher, or extend the sampling time by using
the PC configurator software.
■
NOISE FILTER (SW4)
*
2
Table 10
FILTER SW4-2 SW4-1
Large
ON
OFF
Small
OFF
ON
Without
OFF
OFF
Time constant is set to 50 msec. with the ‘large’ noise filter
setting and to 10 msec. with the ‘small’ noise filter setting.
■
OUTPUT TYPE (SW3 & 1)
Table 11
OUTPUT
SW3-3 SW3-2 SW1-4 SW1-3 SW1-2 SW1-1
0
–
20mA
OFF ON OFF ON OFF OFF
-2.5 – +2.5V
ON OFF ON OFF OFF ON
-10 – +10V
OFF OFF ON OFF ON OFF
■
OUTPUT TYPE / PC CONFIG (SW1)
*
2
Table 12
OUTPUT
SW1-4 SW1-3 SW1-2 SW1-1
0 – 20mA
OFF
ON
OFF
OFF
-2.5 – +2.5V
ON
OFF
OFF
ON
-10 – +10V
ON
OFF
ON
OFF
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) DIP SW setting: Check that the switches are set to ap
-
propriate positions.
3) Power input voltage: Check voltage across the terminal
10 – 12 (AC) or 11 – 12 (DC) with a multimeter.
4) Input: Check that the input signal is within 0 – 100% of
full-scale.
5) Output: Check that the load resistance meets the de
-
scribed specifications.
MAINTENANCE
Regular calibration procedure is explained below:
■
CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit using the PC Configurator
Software (model: M3LPACFG).