17
M3LM OPERATING MANUAL EM-2663-B Rev.4
7.2.3.2 PC configuration
• DC current output
SW1-4
SW1-3
SW1-2
SW1-1
OFF
ON
OFF
OFF
• DC voltage output (narrow spans) [maximum range: -2.5 to +2.5 V DC]
SW1-4
SW1-3
SW1-2
SW1-1
ON
OFF
OFF
ON
• DC voltage output (wide spans) [maximum range: -10 to +10 V DC]
SW1-4
SW1-3
SW1-2
SW1-1
ON
OFF
ON
OFF
7.2.4 FRONT CONTROL BUTTON LOCK
You can lock the button operation on the front panel to prevent inadvertent operation.
This function is applicable to the firmware 2.02 or higher version. Confirm the firmware version on the specification label
on the side of the transmitter.
LOCK
SW2-1
Unlock
OFF
Lock
ON