background image

M2LR

P. 2 / 6

EM-5057-A Rev.2

When you program the transmitter module, two configura-
tion modes are available: Field Configuration using DIP SW 
/ control buttons, and PC Software.
The internal DIP switches are used to configure input and 
output type.  Once the module is configured, precise ranges 
are  set  up  with  the  front  control  buttons  using  a  simula-
tor connected to the input terminals and a multimeter con-
nected to the output terminals as a reference.
The calibrated input and output ranges are stored in the in-
ternal memory.  The module reads the DIP-switch-calibrat-
ed configuration only once after the power supply is turned 
on.  Set the switches with the power supply removed.
Selectable I/O type and ranges are listed in Table 6 and 7.

 DIP SW CONFIGURATION MODE

Turn the SW2-8 OFF to enable the DIP SW (Field Configu-
ration) mode as shown in Table 1.
See Table 2 to configure the input and Table 4 for the out-
put.

 PC CONFIGURATION MODE

Turn the SW2-8 ON to enable the PC Configuration mode as 
shown in Table 1.  All programmable features can be set up 
on a PC regardless of other DIP SW setting except that the 
output type must be selected with the DIP SW1-1 through 
SW1-4 (See Table 5).
For detailed information on the PC configuration, refer to 
the M2LRCFG instruction manual.

EXTERNAL VIEWS

1 2 3 4 5 6 7 8

OFF

ON

OFF

ON

1 2 3 4

SW2

SW1

Configuration DIP SW

■ 

FRONT VIEW

■ 

SIDE VIEW

Configurator Jack

DOWN Button

UP Button

MODE Button

LED3 (LD3)

LED2 (LD2)

LED1 (LD1)

CONFIGURATION MODE & DIP SW SETTINGS

 CONFIGURATION MODE (SW2) 

Table 1

MODE 

SW2-8

DIP SW 

OFF 

Configuration mode can be 

   

PC (*) 

ON 

confirmed with the front LED.

(*) Factory setting

 INPUT TYPE (SW2) 

Table 2

INPUT 

SW2-7 

SW2-6 

SW2-5

JPt 100

 (JIS ’89)

 

OFF 

OFF 

OFF  

Pt 100

 (JIS ’89)

 

ON 

OFF 

OFF  

Pt 100

 (JIS ’97, IEC)

 

OFF 

ON 

OFF

Pt 50Ω

 (JIS ’81)

 

ON 

ON 

OFF  

Pt 1000 

OFF 

OFF 

ON   

Cu 10 @25°C 

ON 

OFF 

ON 

User’s table 

ON 

ON 

ON 

 BURNOUT (SW2) 

Table 3

BURNOUT 

SW2-1 

SW2-2

No burnout 

OFF 

OFF 

Upscale (*) 

OFF 

ON 

Downscale 

ON 

ON

(*) Factory setting

 OUTPUT TYPE (SW2 & 1) 

Table 4

OUTPUT 

SW2-4 SW2-3 SW1-4 SW1-3 SW1-2 SW1-1

0 – 20mA 

OFF  OFF  OFF  ON  OFF  OFF 

-2.5 – +2.5V 

OFF  ON 

ON  OFF  OFF  ON 

-10 – +10V 

ON  OFF  ON  OFF  ON  OFF

 OUTPUT TYPE / PC CONFIG (SW1) 

Table 5

OUTPUT 

SW1-4 

SW1-3 

SW1-2 

SW1-1

0 – 20mA 

OFF 

ON 

OFF 

OFF 

-2.5 – +2.5V 

ON 

OFF 

OFF 

ON 

-10 – +10V 

ON 

OFF 

ON 

OFF

Отзывы: