M2EXM
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5135-B Rev.5 P. 18 / 19
ERROR MESSAGES
DISPLAY
ERROR DESCRIPTION
WHAT TO DO
OVER RANGE U
The input exceeds 105 %.
Return the input signal not exceed 105 %.
OVER RANGE D
The input exceeds lower limit of -5 %.
Return the input signal -5 % or more.
SCALING ERROR U
Input or output scaling value exceeds
999999 (upward).
Return the input or output signal not exceed 999999.
SCALING ERROR D
Input or output scaling value exceeds
-99999 (downward).
Return the input or output signal not lower than -99999.
SETTING ERROR
Setting value error
Return the setting value to normal value.
EEPROM I ERROR
Internal data error
Repair is needed if the display does not recover after the
power is reset.
EEPROM R ERROR
Memory reading error
‘Reset all settings’ in advanced mode.*
1
EEPROM W ERROR
Memory writing error
‘Reset all settings’ in advanced mode.*
1
*1. All setting parameters are initialized. Repair is needed if it does not recover.
Indicated errors vary as follows depending on setting value of display setting.
Error is indicated blinking at upper or lower.
When multiple error occurs, only high priority error is displayed.
Order of priority is EEPROM ERROR, OVER RANGE, SCALING ERROR in descending order.
ERR
OR MESS
A
GES
DISPLAY SETTING
INPUT ENGINEERING
UNIT VALUE
INPUT SCALING
VALUE
PERCENT VALUE OUTPUT ENGINEERING
UNIT VALUE
OUTPUT SCALING
VALUE
OVER RANGE U
—
OVER RANGE D
SCALING ERROR U
(INPUT)
—
—
—
SCALING ERROR D
(INPUT)
SCALING ERROR U
(OUTPUT)
—
—
—
SCALING ERROR D
(OUTPUT)
EEPROM I ERROR
EEPROM R ERROR
EEPROM W ERROR
WIRING INSTRUCTIONS
■
SCREW TERMINAL
Torque: 0.8 N·m
■
SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm
2
(AWG 22 to 16)
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd, Nichifu Co.,ltd
6 (.24) max
3.3 (.13) max
mm (inch)
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Check DIP switch setting.
3) Power input voltage: Check voltage across the terminal
10 – 11 with a multimeter.
4) Input: Check that the input signal is within 0 – 100% of
the full-scale.
5) Output: Check that the load resistance meets the de-
scribed specifications.