MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Without linearization, warm up the unit for at least 10 
minutes.  Apply 0%, 25%, 50%, 75% and 100% input signal.  
Check that the output signal for the respective input sig-
nal remains within accuracy described in the data sheet.  If 
the output signal is out of accuracy, when the input display 
value is out of accuracy, perform the teach, when the input 
display value is correct but the output is out of accuracy, 
perform the output fine adjustment.  Refer to the operating 
manual (EM-5983-B), when adjusting with front buttons.  
Refer to the M1ECFG users manual (EM-5981), when ad-
justing with M1E Configurator Software (model: M1ECFG). 
And then follow the procedure shown below.

• OUTPUT FINE ADJUSTMENT

1) Set the simulated input to 0 %, and adjust the output 

signal to 0 % by [82]/[182] Output Zero fine adjust.

2) Set the simulated input to 100 %, and adjust the output 

signal to 100 % by [83]/[183] Output Span fine adjust.

3) Again set the simulated input to 0 %, confirm the output 

signal.

4) If output signal is shifted, repeat the procedure from 1) to 

3).

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

Содержание M1EXM-2

Страница 1: ...validate the CE conformance The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform ity Install lightning surge protectors f...

Страница 2: ...ntiometer input 3 18 Unused 9 Ch2 Potentiometer input 2 19 Power U 10 Ch2 Potentiometer input 1 20 Power V INSTALLATION Pulling out the base while pushing the lockslider on the top of the unit enables to remove the base from the unit base is not included in the package DIN RAIL MOUNTING SIDE Mounting the unit A Hang the upper hook at the rear side of unit on the DIN rail B Push the lower part of t...

Страница 3: ... of the unit EXTERNAL DIMENSIONS unit mm inch 125 4 92 36 1 42 89 3 50 5 20 5 20 7 28 7 28 45 1 77 4 16 DIN RAIL 35mm wide 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Base is not included in the package MOUNTING REQUIREMENTS unit mm inch 99 3 90 2 M4 SCREW Mounting requirements for base CONNECTION DIAGRAM 11 12 14 15 19 20 CH1 OUTPUT CH1 POTENTIOMETER CH2 POTENTIOMETER 1 4 5 3 3 2 1 Max Min...

Страница 4: ...p button Used to shift through setting parameter and to increase or select setting value Down button Used to shift through setting parameter and to decrease or select setting value Configurator Jack Used to configure with M1E configurator software model M1ECFG At the same time set the lockout setting of the unit to lock WIRING INSTRUCTIONS FOR BASE SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL...

Страница 5: ...is out of accuracy perform the output fine adjustment Refer to the operating manual EM 5983 B when adjusting with front buttons Refer to the M1ECFG users manual EM 5981 when ad justing with M1E Configurator Software model M1ECFG And then follow the procedure shown below OUTPUT FINE ADJUSTMENT 1 Set the simulated input to 0 and adjust the output signal to 0 by 82 182 Output Zero fine adjust 2 Set t...

Отзывы: