background image

JR

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: 

+81(6)6659-8510  E-mail: [email protected]

EM-1663  Rev.8  P. 4 / 4

PROGRAMMABLE ITEMS

The following items can be monitored and programmed.  For detailed explanations, please refer to the Operation Manual for 
Model PU-2x (EM-9255), Section A.

[GROUP 01]

ITEM

MDFY.

DATA INPUT

DISPLAY

CONTENTS

01

S

MAINTENANCE SWITCH (lock command)

0

MTSW: MON.MODE

MONITOR mode: data monitoring only

1

MTSW: PRG.MODE

PROGRAM mode: “P” marked data modifiable

02

P

Alphabets & No.

TG: XXXXXXXXXX

Tag name entry (10 characters max.)

03
04

P

D

Number (%)
No input

OUTPER XXX.XX
OUTTMP XXXXXX

Output status monitor (%) & simulation output
Output temperature monitor *

1

06

D

No input

INPVAL XXXXXX

Input status monitor in 

Ω

.

10

TYPE OF RTD

P
P

31
32

RB-1: Pt 100
RB-2: JPt 100

Pt 100 (JIS ’89)
JPt 100 (JIS ’89)

D
D

33
34

RB-3: Pt 50
RB-4: Ni 508.4

Pt 50 

Ω

 (JIS ’81)

Ni 508.4 

Ω

P

36

RB-6: Pt 100_97

Pt 100 (JIS ’97, IEC)

14
15

P
P

Actual value
Actual value

SCLLOW XXXXXX
SCLHIG XXXXXX

Input range scaling 0% value
Input range scaling 100% value
Use the same temp. unit as selected in ITEM 21.

19

P

Percentage

FINZER

Fine zero adjustment
Initial status shows actual bias (%). 
When data is entered, output (%) is shown.

20

P

Percentage

FINSPN

Fine span adjustment
Initial status shows actual gain (%).
When data is entered, output (%) is shown.

21

P

TEMPERATURE SCALE

0
1
2

TMPSCL: [°C]
TMPSCL: [°F]
TMPSCL: [K]

Program ITEM 21 first before ITEM 14 when °F or K calibration is 
needed.  This procedure is necessary whenever thermocouple type 
is changed.

Modification Code

D: No modification (writing) possible. Used only for monitoring (reading).
S: Modifiable at any time.
P: Modifiable only when the MAINTENANCE SWITCH is in the “PRG” mode.

*1. Temperature is indicated in the unit selected in ITEM 21.