background image

JPS3

P.  / 5

EM-575 Rev.

HARDWARE SETTING

• Noise Filter

‘High’ setting is used for the input frequency ≤10 Hz.
‘Low’ setting is used for the input frequency ≤500 Hz.
For mechanical contact input, ‘High’ setting is recommend-
ed to prevent typical chattering from counting.
DO  NOT  change  the  factory  settings  of  SW1-1  through 
SW1-6 and SW2-1 through SW2-6.

INPUT 1

INPUT 2

NOISE FILTER

SW1-7

SW1-8

SW2-7

SW2-8

High

ON

OFF

ON

OFF

Low

OFF

ON

OFF

ON

None

OFF

OFF

OFF

OFF

The switches in the table are set at the factory according to 
the Ordering Information Sheet.

5

4

3

2

1

0

9 8 7 6

1

2

3

4

5

6

7

8
1

2

3

4

5

6

7

8

Output Voltage Adj.

Unused
Unused
Unused

One-shot Pulse

Width Adj.

Input Type Selectors

Input Monitor LED (PL2)

Modular Jack

Output Monitor LED

Input Monitor LED (PL1)

The JPS3 is programmed and calibrated at the factory according to 

the Ordering Information Sheet.

Please refer to the instruction manual for the model under “Software

Setting” when you need to modify certain specifications.

DO NOT change setting of unused switches and potentiometers.

SOFTWARE SETTING

Please refer to the Operation Manual for Model PU-2x (EM-9255), Section B: (B-1) Introduction, (B-2) General Operation 
Description, (B-3) Operation Flowchart for general information.

[GROUP 01]

ITEM

MDF.

CODE

INPUT DATA

EXAMPLE (EXAMPLE)

DEFAULT

CONTENTS

0

S

0

MTSW : MON.MODE
MTSW : PRG.MODE

N/A

MAINTENANCE SWITCH
0  : Data indication only.
1  : All ‘P’ marked parameters are modifiable.

0

P

Alphanumeric TG : XXXXXXXXXX

N/A

Tag name entry (10 characters max.)

0

P

Numeric

CT1 : XXXXXX

0*

1

Total input 1 pulses (any count selectable)

0

P

Numeric

CT2 : XXXXXX

0*

1

Total input 2 pulses (any count selectable)

05

P

Numeric

IN : XXXXXX

Input pulse set count (1 to 1 000 000)

06

P

Numeric

OUT : XXXXXX

Output pulse set count (1 to 1 000 000)

07

P

Numeric (Hz)

FRQ : XXXX.XHz

0.0

Max. output frequency limit (0.5 to 100000.0 Hz)

08

P

Numeric (s)

SMP : X.XXs

0.0

Sampling time (0.01 to 100.00 s)

09

D

No input

SW : IN_V  1/20
SW : IN_V  1/10
SW : IN_V  1/5
SW : IN_V  1/2
SW : IN_V  1/1
SW : IN_V  5/1
SW : IN_V  10/1
SW : IN_OC, mA
SW : no use
SW : no use

N/A

Input specifications
SW = 0, Voltage input, Sensitivity scale = 1/20
SW = 1, Voltage input, Sensitivity scale = 1/10
SW = 2, Voltage input, Sensitivity scale = 1/5
SW = 3, Voltage input, Sensitivity scale = 1/2
SW = 4, Voltage input, Sensitivity scale = 1/1
SW = 5, Voltage input, Sensitivity scale = 5/1
SW = 6, Voltage input, Sensitivity scale = 10/1
SW = 7, Open collector, mechanical contact or two-wire current input
SW = 8, (not used)
SW = 9, (not used)

0

P

0

IN_EDGE : 0
IN_EDGE : 1

*

2

Count mode
Count at pulse rise
Count at pulse sink

*1. Reset to 0 when the power is lost.

*2. Factory set.  DO NOT change this setting. 

Modification Code

D : No modification (writing) possible.  Used only for monitoring (reading).

S : Modifiable at any time.

P : Modifiable only when the MAINTENANCE SWITCH is in the ‘PRG’ mode.

ROM Version Indication

[GROUP 00] [ITEM 99]