background image

GR8-EM

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8621 Rev.5  P. 2 / 15

COMPONENT IDENTIFICATION

Connector for
Power Supply

Terminating Resistor
Setting SW

Status Indicator LED

Function Setting DIP SW

1

SW1

2

3

4

5

6

7

8

ON

RJ-45 Connector for 
Ethernet

Connector for
RS-485 Communication

 

FRONT VIEW

 

RIGHT SIDE VIEW

 

STATUS INDICATOR LED

ID

Color

Light

Module Status

RUN

Green

Blinking (1-sec cycle)

Normal mode

Blinking in low speed (2-sec cycle)

Maintenance mode (with SW1-2 ON)

Blinking in high speed 
(0.4-sec cycle)

Error (device error when the unit wouldn’t recover even after power 
reactivation)

OFF

Power is off or device error

ERR

Red

ON

Data error from RS-485 device

RD

Green

ON

Receiving data from the paired RS-485 station

SD

Green

ON

Sending data to the paired RS-485 station

LINK

Green

ON

Being linked with 10BASE or 100BASE

Blinking

Sending/receiving data

OFF

No link detected

LK100

Green

ON

Being linked with 100BASE

OFF

Being linked with 10BASE or Not linked

 

DIP SW SETTING

(*) Factory default setting

• IP Address

SW1-1

Mode

Function

OFF (*)

Normal mode

Set with configurator

ON

Factory default 
mode

When starting up with the SW ON, the unit temporarily operates by the factory default settings 
of network configuration, user ID and password.
The stored settings, however, are maintained and the unit returns to the original settings upon 
restarting at normal mode.  When network settings are changed during factory default mode, 
the changed settings are stored.    

• Maintenance mode

SW1-2

Mode

Function

OFF (*)

Normal mode

Normal operation

ON

Maintenance mode

Stop output (Modbus function 05, 06, 15, 16 are disabled)

Note: Be sure to set unused SW1-3 through 1-8 to OFF.

 

TERMINATING RESISTOR SETTING SW

• Terminating resistor

TERM

INCORPORATED TERMINATING RESISTOR

OFF

Disabled

ON (*)

Enabled

Содержание GR8-EM

Страница 1: ...he user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform ity POWER INPUT RATING OPERATIONAL RANGE Locate the powe...

Страница 2: ...data to the paired RS 485 station LINK Green ON Being linked with 10BASE or 100BASE Blinking Sending receiving data OFF No link detected LK100 Green ON Being linked with 100BASE OFF Being linked with...

Страница 3: ...RUCTIONS EURO TYPE CONNECTOR TERMINAL POWER SUPPLY Applicable connector MSTB2 5 3 ST Phoenix Contact attached to the product Applicable wire size 0 2 2 5 mm2 Stripped length 7 mm Recommended pin termi...

Страница 4: ...orm internal communication or the power can not be supplied to these I O modules Confirm that the locking clamps of the unit are set Insert the unit straight in perpendicularly to the rail such that t...

Страница 5: ...f unit on the DIN rail Push in the lower in keeping pressing the unit to the DIN rail B To remove the unit push down the DIN rail adaptor using a minus screwdriver Pull out the lower part of the unit...

Страница 6: ...SIONS unit mm inch 4 16 5 20 73 2 87 55 2 17 73 2 87 55 2 17 115 4 53 6 24 7 28 115 4 53 6 24 7 28 6 24 7 28 3 12 COUPLED WITH DL8 SINGLE USE 1 24 94 3 12 24 94 CONNECTION DIAGRAM RJ 45 CONNECTOR To o...

Страница 7: ...sent from the host for a certain time RS 485 Modbus RTU Protocol Modbus RTU Configuration Bus type multi drop Standard Conforms to TIA EIA 485 A Communication Half duplex asynchronous no procedure Tra...

Страница 8: ...d When the number of Cache areas reaches 100 following queries will be handled as normal queries without Cache function Note If no query is sent from the host for 10 seconds the Cache is disabled If d...

Страница 9: ...modules Hub DL8 Client 24V DC power DL8 GR8 EM I O modules Note It is not available to supply the power via DL8 Supply the power with the connector for power supply COUPLED WITH DL8 Communication Ada...

Страница 10: ...point etc by users Though the web server is designed for applicable to many web browsers supporting HTML5 operation with all web browsers or environment cannot be guaranteed Please notice that even w...

Страница 11: ...information or setting view Pressing LANG button enables to select the language between English and Japanese PASSWORD Set the user name and password to be required for user authentication to connect...

Страница 12: ...5 Subnetmask Set the Subnet Mask for the unit Range 0 0 0 0 to 255 255 255 255 Default gateway Set the router address connected to external network 0 0 0 0 not used is available for local network whic...

Страница 13: ...et the transfer rate Choose among 2400 4800 9600 19200 38400 57600 or 115200 bps Parity bit Set the parity bit Choose among None Odd or Even Stop bit Set the stop bit Choose between 1 bit and 2 bits R...

Страница 14: ...e unit System up time Operating time from power on Modbus TCP STATISTICS ITEM DESCRIPTION Receive frames Received request numbers of Modbus TCP Error receive frames Numbers of error frame of received...

Страница 15: ...f the unit ITEM DESCRIPTION Reboot the device Clicking Reboot enables to restart the unit Update the firmware Firmware update is available in order to add new functions and improve operations Download...

Отзывы: