DL8
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-7691-A Rev.6 P. 2 / 4
COMPONENT IDENTIFICATION
Status Indicator LED
Miniature Jack Connector for DLCFG
RJ-45 Connector for Ethernet
Logging Button (Type C & D)
SD Button (Type C & D)
SD Card Slot (Type C & D)
Miniature Jack Connector for R8CFG
Internal Bus Connector
DPLX
LNK
POWER
LOGGING
SD CARD
SEND
COM
ERROR
I/O
LOGGING
SD CARD
On
8
7
6
5
4
3
2
1
CFG
Function Setting DIP SW
8
7
6
5
4
3
2
1
On
Connector for Power Supply (Exc. supply),
RUN Contact Output
Ethernet Indicator LED
■
STATUS INDICATOR LED
LED
Color
Function
POWER
Green
ON at device operating normally
Blinking at Ethernet LINK error
Blinking before obtaining DHCP ad-
dress
LOGGING Green ON at logging (Type C & D)
SD CARD
Green
ON during SD card mounted
Blinking at reading/writing SD card
(Type C & D)
SEND
Green Blinking at e-mailing
COM
Green
Blinking at communication
(except Modbus/TCP master)
ERROR
Red
ON at error
• R8 I/O module reading error
• SD card access error
• SD card insufficient capacity
■
ETHERNET INDICATOR LED
LED
Color
Function
DPLX
Amber ON at full duplex
LNK
Green ON at link
■
POWER SUPPLY (EXC. SUPPLY), RUN CONTACT OUT-
PUT CONNECTOR TERMINAL ASSIGNMENT
Printed-circuit board connector (Phoenix Contact)
Unit side connector: MSTBV2,5/5-GF-5,08AU
Cable side connector: TFKC2,5/5-STF-5,08AU
■
POWER SUPPLY (EXC. SUPPLY), RUN CONTACT OUTPUT CONNECTOR TERMINAL ASSIGNMENT
Printed-circuit board connector (Phoenix Contact)
Unit side connector: MSTBV2,5/5-GF-5,08AU
Cable side connector: TFKC2,5/5-STF-5,08AU
No.
ID
FUNCTION
1
24V
Power supply (exc. supply) 24 V DC
2
0V
Power supply (exc. supply) 0 V DC
3
RUN RUN contact output
4
RUN RUN contact output
5
FE
Power supply (exc. supply) earth
1
2
3
4
5
■
FRONT SWITCH
(*) Factory setting
•
MINIATURE JACK for DLCFG (SW1)
SW1
FUNCTION
OFF (*)
Set with DLCFG
ON
FTP transfer and reporting e-mail reading
•
REPORTING E-MAIL (SW2)
*
1
SW2
E-MAIL OPERATON
OFF (*)
Available
ON
Not Available
*1. Type B, C and D only.
Note: Be sure to set unused SW3 through 8 to OFF.
■
LOGGING BUTTON
Pressing and holding 1 second starts and stops logging.
■
SD BUTTON
Pressing and holding for 4 seconds turns SD CARD LED off
and makes the card removable.