background image

M3LDY

P. 6 / 7

EM-2664-A

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

Phone: +81(6)6659-8201   Fax: +81(6)6659-8510   E-mail: [email protected]

 PREPARATION (e.g. M3LDY-R/A)

1)  Mount the DIP-SW-configured M3LDY on to a DIN rail.
2) Connect the M3LDY to a simulator and a multimeter 

and to a DC power source as shown below.

3)  Turn the power supply on and wait for 10 minutes.

2

3

7

8

11

12

M3LDY

Multimeter

Simulator

+

DC Power Source

+ –

+

 INPUT & OUTPUT RANGING

[Example]

Setting input to 4 – 20mA DC and output to 1 – 5V DC
1)  Run  Mode:  Confirm  that  the  green  LED  is  blinking 

(model M3LDY-x/A) or the green LED turns on (model 
M3LDY-x/B).

2)  Input Configuration Mode: Press MODE button for long-

er than 5 seconds until the LD1 red LED is ON and the 

LD2 red LED is blinking.

3)  0%  Input  Ranging:  Apply  the  desired  minimum  input 

level (e.g. 4mA) from the simulator and push DOWN but-
ton until the LD1 blinks for approx. 2 sec. and then turns 
OFF.  When you release the button, the LD1 is returned 
to ON.  

  The blinking LD1 means that the value is stored in the 

memory.  If the LED does not change, the entered level 
may be inappropriate:  too small a span, or out of usable 
range (same for all steps).

4)  100% Input Ranging: Apply the desired maximum input 

level (e.g. 20mA) from the simulator and push UP button 
until the LD1 blinks for approx. 2 sec. and then turns 
OFF.  When you release the button, the LD1 is returned 
to ON.

5)  Output  Configuration  Mode:  Push  MODE  button  and 

confirm that the LD3 red LED instead of LD2 is blinking.

6)  0% Output Ranging: Increase or decrease the simulated 

input until the meter shows the desired minimum out-
put level (e.g. 1V).  Push DOWN button until the LD1 
blinks for approx. 2 sec. and then turns OFF.  When you 
release the button, the LD1 is returned to ON.

7)  100%  Output  Ranging:  Increase  or  decrease  the  simu

-

lated input until the meter shows the desired maximum 

output  level  (e.g.  5V).    Push  UP  button  until  the  LD1 

blinks for approx. 2 sec. and then turns OFF.  When you 
release the button, the LD1 is returned to ON.

8)  Run Mode: Programming complete, push MODE button 

and confirm that only the LD1 green LED is blinking.

 ZERO & SPAN ADJUSTMENTS

After the transmitter is installed and operational, fine zero 
and span tuning can be performed as explained below.  Both 

zero and span are adjustable within ±15%.
1)  Run  Mode:  Confirm  that  the  green  LED  is  blinking 

(model M3LDY-x/A) or the green LED turns on (model 
M3LDY-x/B).

2) Fine Zero Calibration Mode: Press MODE button for 1 

or 2 seconds until the LD1 red LED is ON and the LD2 
green LED is blinking.

3) Use UP (increase) and DOWN (decrease) buttons to ad-

just the output to 0%.

4) Fine Span Calibration Mode: Push MODE button and 

confirm that the LD3 green LED instead of LD2 is blink-
ing.

5)  Use UP (increase) and DOWN (decrease) buttons to ad

-

just the output to 100%.

6)  Run Mode: Push MODE button and confirm that only the 

LD1 green LED is blinking.

Note 1: Calibration steps can be skipped when not needed 
by repeating pushing MODE buttons.
Note 2: There is no stated order of setting 0% and 100% 
levels or no limitation of entering values for multiple times 
within one step of Calibration Mode.  Signal level is stored 
each time the respective UP or DOWN button is pressed.

 I/O RANGE LABEL

Blank I/O range labels are included in the product pack-
age.  Write in the configured ranges and put the label on 
the side as shown below.

INPUT
OUTPUT

I/O Range Label (included in the product package)

Содержание Current Loop Supply M3LDY

Страница 1: ...rs for the power source input and output connected to the unit COSEL Model NAC 04 472 TDK Model ZCAT 3035 1330 or equivalent is recommended Install lightning surge protectors for those wires connect e...

Страница 2: ...NG Set the unit so that its DIN rail adaptor is at the bottom Position the upper hook at the rear side of the unit on the DIN rail and push in the lower When removing the unit push down the DIN rail a...

Страница 3: ...ting no extra space is needed between units DIN RAIL 35mm wide EXTERNAL INTERNAL VIEWS 8 7 6 5 4 3 2 1 ON OFF ON OFF 4 3 2 1 Configuration DIP SW 10 11 12 7 8 9 4 5 6 1 2 3 Configurator Jack DOWN Butt...

Страница 4: ...mable features can be set up on a PC regardless of other DIP SW setting except that the output type must be selected with the DIP SW1 1 through SW1 4 See Table 6 For detailed information on the PC con...

Страница 5: ...ntrol Buttons Red LED OFF ON Blink RUN MODE LD2 LD3 A G RUN MODE LD2 LD3 G R LD1 LD2 LD3 LD1 LD2 LD3 0 INPUT CONFIGURED 100 INPUT CONFIGURED INPUT CALIBRATION MODE LD1 OUTPUT CALIBRATION MODE LD2 LD3...

Страница 6: ...t level e g 1V Push DOWN button until the LD1 blinks for approx 2 sec and then turns OFF When you release the button the LD1 is returned to ON 7 100 Output Ranging Increase or decrease the simu lated...

Страница 7: ...tion RUN Mode Option A The transmitter is configured via PC and is in normal operating conditions DIP SW Configuration RUN Mode The transmitter is configured via DIP SW and is in normal operating cond...

Отзывы: