TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

49.1 (1.93)

33 (1.30)

39 (1.54)

34 (1.34)

28 (1.10)

22 (.87)

2–3.5 dia. MTG HOLE

14

(.55)

79 (3.11)

5 (.20) dia.

3–M3 SCREW

TERMINAL COVER

R1

R0

12V

 

CONNECTION DIAGRAM

12V

R0

CLSP

PULSE INPUT

R1

+

+

POWER SUPPLY

PULSE OUTPUT

WIRING INSTRUCTIONS

 

SOLDERLESS TERMINAL  unit: mm (inch)

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.  Solder-
less terminals with insulation sleeve do not fit.  
Applicable wire size: 0.3 – 0.75 mm

2

3.2 (.13) dia.

4 min.

(.16)

12 (.47) max.

6 max

.

(.24)

3 (.12) max.

 

INSERTING WIRES

Insert the output and power supply wires from the direction 
as shown below and tighten firmly (torque 0.5 N·m).

R1

R0

12V

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

12V – R0 with a multimeter.

3) Input:  Check the input signal.
4) Output:  Check the output signal.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

CLSP

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-9237  Rev.3  P. 2 / 2