TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■
EXTERNAL DIMENSIONS unit: mm (inch)
49.1 (1.93)
33 (1.30)
39 (1.54)
34 (1.34)
28 (1.10)
22 (.87)
2–3.5 dia. MTG HOLE
14
(.55)
79 (3.11)
5 (.20) dia.
3–M3 SCREW
TERMINAL COVER
R1
R0
12V
■
CONNECTION DIAGRAM
12V
R0
CLSP
PULSE INPUT
R1
+
+
–
POWER SUPPLY
PULSE OUTPUT
WIRING INSTRUCTIONS
■
SOLDERLESS TERMINAL unit: mm (inch)
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable. Solder-
less terminals with insulation sleeve do not fit.
Applicable wire size: 0.3 – 0.75 mm
2
3.2 (.13) dia.
4 min.
(.16)
12 (.47) max.
6 max
.
(.24)
3 (.12) max.
■
INSERTING WIRES
Insert the output and power supply wires from the direction
as shown below and tighten firmly (torque 0.5 N·m).
R1
R0
12V
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
12V – R0 with a multimeter.
3) Input: Check the input signal.
4) Output: Check the output signal.
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.