background image

EM-3118  Rev.4  P. 1 / 3

MG CO., LTD. www.mgco.jp

5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing us.  Before use, please check con-
tents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact our sales office or representatives.

 

PACKAGE INCLUDES:

Signal conditioner
(body + base input resistor)..................................(1)
Input resistor is provided only with current input type.

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• The equipment must be mounted inside a panel.
• Insert noise filters for the signal input and output con-

nected to the unit.  COSEL Model NAC-06-472 or equiva-
lent is recommended.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

• Install lightning surge protectors for those wires connect-

ed to remote locations.

 

GENERAL PRECAUTIONS

• Before you remove the unit from its base socket or mount 

it, turn off the power supply and input signal for safety.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -5 to +55°C     

(23 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

COMPONENT IDENTIFICATION

Input Resistor

Body

Base Socket

Specifications

Zero Adj.

Span Adj.

Connection

Diagram

(side)

INSTALLATION

Pull out the body in pressing the clamps located at the top 
and bottom of the unit for separate the body from the base 
socket.

 

DIN RAIL MOUNTING

DIN Rail

35mm wide

Spring Loaded

DIN Rail Adaptor

Set the base socket so that 
its DIN rail adaptor is at 
the bottom.  Hang the upper 
hook at the rear side of base 
socket on the DIN rail and 
push in the lower.  When 
removing the socket, push 
down the DIN rail adaptor 
utilizing a minus screwdriv-
er and pull.

 

WALL MOUNTING

Refer to “EXTERNAL DIMENSIONS.”

SIGNAL TRANSMITTER

(isolated)

MODEL

BVS