manualshive.com logo in svg
background image

B5VS

P. 2 / 2

EM-53 Rev.3

TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the con-
nection diagram on the front of the unit.

 EXTERNAL DIMENSIONS  unit: mm (inch)

 CONNECTION DIAGRAM

7 8

5 6

3 4

1 2

94 (3.70)

25 (.98)

41 (1.61)

[3.3 (.13)]

• When mounting, no extra space is needed between units.

DIN RAIL

35mm wide

8–M3.5 SCREW

7.3 (.29)

3 (.12)

+

INPUT

3
4
1
2

*  

Short across the terminals for current input.

**

DC ammeter's internal resistance 10 ohms max.

*

**

8
7

+

mA

MONITOR

+

+

LOAD

6

5

OUTPUT

24VDC

4 – 20mADC

CHECKING

1)  Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2)  Input:  Check that the input voltage is within 0 – 100% of 

full-scale.

3)  Output:  Check that the load is within the permissible 

limit including wiring resistance.  

   

 

 

       Supply Voltage (V) – 12 (V)

  Load Resistance (Ω) = –––––––––––––––––––––––– 

   

 

 

 

         0.02 (A)

     

 

 

(including leadwire resistance)

4)  When you check the output signal, connect an ammeter 

of  which  the  internal  resistance  is  of  10Ω  max.  to  the 
monitor terminals.

ADJUSTMENT PROCEDURE

This  unit  is  calibrated  at  the  factory  to  meet  the  ordered 
specifications,  therefore  you  usually  do  not  need  any  cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 
following.

 HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.
1)  ZERO:  Apply 0% input and adjust output to 0%.
2)  SPAN:  Apply 100% input and adjust output to 100%.
3)  Check ZERO adjustment again with 0% input.
4)  When  ZERO  value  is  changed,  repeat  the  above  proce-

dure 1) – 3).

MAINTENANCE

Regular calibration procedure is explained below:

 CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%,  75%  and  100%  input  signal.    Check  that  the  output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance,  recalibrate  the  unit  according  to  the “ADJUST-
MENT PROCEDURE” explained earlier.

M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship 
during the 36-month period following the date that such product was originally purchased if such product has been used under 
normal operating conditions and properly maintained, M-System’s sole liability, and purchaser’s exclusive remedies, under this 
warranty are, at M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is 
defective under the terms of this warranty.  To submit a claim under this warranty, the purchaser must return, at its expense, the 
defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, 
EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICU-
LAR PURPOSE.  M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES 
OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-
8510, E-mail: [email protected]