background image

AS4R

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-1606  Rev.14  P. 4 / 5

ITEM

MDF.

CODE 

DATA

CONTENTS

DEFAULT SETTING

25

2

0 – 7

RTD type
0: JPt 100 (JIS ’89), 1: Pt 100 (JIS ’89), 
2: Pt 100 (JIS ’97, IEC), 3: Pt 50 Ω (JIS ’81)
4: Ni 508.4 Ω, 5: Pt 1000, 6: Ni 100, 7: Cu 10 @25°C 

2: Pt 100 (JIS ’97, IEC)

*1. It operates simultaneously with the display unit of ITEM 24.  Refer to the table 1 for available setting range.
*2. Quad alarm trip type only

Table 1: USABLE RANGE

RTD

USABLE RANGE

°C

°F

K

JPt 100 (JIS ’89)

 

-235 –  +560.0

  -391 – +1040

  38.2 –  833.2

Pt 100 (JIS ’89)

 

-240 –  +900.0

  -400 – +1652

  33.2 –  1173

Pt 100 (JIS ’97, IEC)

 

-240 –  +900.0

  -400 – +1652

  33.2 –  1173

Pt 50 Ω (JIS ’81)

 

-235 –  +700.0

  -391 – +1292

  38.2 –  973.2

Ni 508.4 Ω

  -100.0 –  +330.0

  -148.0  – +572.0

  173.2 –  603.2

Pt 1000

 

-240 –  +900.0

  -400 – +1652

  33.2 –  1173

Ni 100

  -100.0 –  +250.0

  -148.0  – +482.0

  173.2 –  523.2

Cu 10 @ 25°C

 

-210 –  +310.0

 

-346  – +590.0

  63.2 –  583.2

* Minimum step
     -199.9 to 999.9: 0.1 
     Not greater than -200, not lower than 1000: 1

TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the connection diagram on the top of the unit.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

• When mounting, no extra space is needed between units.

5

6

7

8

2

1

11

10

80 (3.1

5)

40 (1.57)

50 (1.97)

7.8 (.31)

2

4.5 (.18) dia.

MTG HOLE

25 (.98) deep

11

M3.5

SCREW

3

9

4

For wiring connection, refer to “TERMINAL CONNECTIONS” and wire correctly.
Fire, electric shock and failure cause if wire are incorrectly connected.

80 (3.1

5)

50 (1.97)

103 (4.06)

132 (5.20)

20 (.79)

[3.3 (.13)]

CLAMP

(top & bottom)

DIN RAIL

35mm wide

Отзывы: