TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the connection diagram on the top of the unit.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

76 (2.99) dia.

40 (1.57)

52.5 (2.07)

1 (.04)

60.9 (2.40)

46 (1.81)

50 (1.97)

4–M3 (.12) TAP

6 (.24) deep

1 2 3 4

5 6

 

CONNECTION DIAGRAM

1

2

3

3

2

1

POTENTIOMETER

max.

min.

+

+

LOAD

6

5

OUTPUT

24V DC

4 – 20mA DC

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.6 N·m

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Input:  Check voltage across the terminal 2 (+) – 3 (–) 

with a voltmeter to show 0V at 0% potentiometer input 

and the same voltage as that across 1 (+) – 3 (–) at 100% 

input.

3) Output:  Check that the load is within the permissible 

limit including wiring resistance.  

Load Resistance (Ω) = 

Supply Voltage (V) – 13 (V)

0.02 (A)

(including leadwire resistance)

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory with the total resist-
ance input, therefore you do not need any calibration if you 
use the potentiometer’s total resistance.
When you do not use the total resistance or in case of regu-
lar calibration, adjust the output as explained in the follow-
ing.  Zero and Span adjustments are located behind the top 
cover.  Release the knurled knobs and open the cover.

1

2

3

4

5

6

VR1

VR2

 

HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.

1) ZERO:  Apply 0% input and adjust output to 0% with the 

VR1.

2) SPAN:  Apply 100% input and adjust output to 100% with 

the VR2.

3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-

dure 1) – 3).

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.