TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the top of the unit.
■
EXTERNAL DIMENSIONS unit: mm (inch)
76 (2.99) dia.
40 (1.57)
52.5 (2.07)
1 (.04)
60.9 (2.40)
46 (1.81)
50 (1.97)
4–M3 (.12) TAP
6 (.24) deep
1 2 3 4
5 6
■
CONNECTION DIAGRAM
1
2
3
3
2
1
POTENTIOMETER
max.
min.
+
–
+
–
LOAD
6
5
OUTPUT
24V DC
4 – 20mA DC
WIRING INSTRUCTIONS
■
SCREW TERMINAL
Torque: 0.6 N·m
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Input: Check voltage across the terminal 2 (+) – 3 (–)
with a voltmeter to show 0V at 0% potentiometer input
and the same voltage as that across 1 (+) – 3 (–) at 100%
input.
3) Output: Check that the load is within the permissible
limit including wiring resistance.
Load Resistance (Ω) =
Supply Voltage (V) – 13 (V)
0.02 (A)
(including leadwire resistance)
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory with the total resist-
ance input, therefore you do not need any calibration if you
use the potentiometer’s total resistance.
When you do not use the total resistance or in case of regu-
lar calibration, adjust the output as explained in the follow-
ing. Zero and Span adjustments are located behind the top
cover. Release the knurled knobs and open the cover.
1
2
3
4
5
6
VR1
VR2
■
HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0% with the
VR1.
2) SPAN: Apply 100% input and adjust output to 100% with
the VR2.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
MAINTENANCE
Regular calibration procedure is explained below:
■
CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.