manualshive.com logo in svg
background image

TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the connection diagram on the top of the unit.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

76 (2.99) dia.

40 (1.57)

52.5 (2.07)

1 (.04)

60.9 (2.40)

46 (1.81)

50 (1.97)

4–M3 (.12) TAP

6 (.24) deep

1 2 3 4

5 6

 

CONNECTION DIAGRAM

1

2

3

3

2

1

POTENTIOMETER

max.

min.

+

+

LOAD

6

5

OUTPUT

24V DC

4 – 20mA DC

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.6 N·m

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Input:  Check voltage across the terminal 2 (+) – 3 (–) 

with a voltmeter to show 0V at 0% potentiometer input 

and the same voltage as that across 1 (+) – 3 (–) at 100% 

input.

3) Output:  Check that the load is within the permissible 

limit including wiring resistance.  

Load Resistance (Ω) = 

Supply Voltage (V) – 13 (V)

0.02 (A)

(including leadwire resistance)

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory with the total resist-
ance input, therefore you do not need any calibration if you 
use the potentiometer’s total resistance.
When you do not use the total resistance or in case of regu-
lar calibration, adjust the output as explained in the follow-
ing.  Zero and Span adjustments are located behind the top 
cover.  Release the knurled knobs and open the cover.

1

2

3

4

5

6

VR1

VR2

 

HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.

1) ZERO:  Apply 0% input and adjust output to 0% with the 

VR1.

2) SPAN:  Apply 100% input and adjust output to 100% with 

the VR2.

3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-

dure 1) – 3).

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

6M

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-4215  Rev.5  P. 2 / 2

Отзывы: