54U
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6487-A Rev.12 P. 15 / 26
Change Setting
(SETTINGS)
Demand Setting
(DEMAND)
Energy Setting
(ENERGY)
Average current
(I)
DIN : External discrete input
1 thr. 60 : Minutes (30)
Average power
(POWER)
DIN : External discrete input
1 thr. 60 : Minutes (30)
Pulse output 1
(COUNT1)
*
4
Pulse weight 1
(WEIGHT1)
0.1 thr. 10 000.0 :
kWh / kvarh / kVAh (1.0)
Pulse width 1
(DURATION1)
100 thr. 2 000 ms (100 ms increments)
(100)
Tariff switching
(TARIFF)
DISABLE (
*
)
ENABLE
∗
3. 0.1
≤
T1.5 character length < T3.5 character length
≤
6.0
*
4. Refer to Modbus - Setting – Energy setting – Energy countt type, for selectable options.
Pulse output 2
(COUNT2)
*
4
Pulse weight 2
(WEIGHT2)
0.1 thr. 10 000.0 :
kWh / kvarh / kVAh (1.0)
Pulse width 2
(DURATION2)
100 thr. 2 000 ms (100 ms increments)
(100)
(
*
) or ( ) : Factory setting
Modbus setting
(MODBUS)
Modbus address
(ADDRESS)
1 thr. 247 (1)
Baud rate
(BAUDRATE)
1200 bps
2400 bps
4800 bps
9600 bps
19200 bps
38400 bps (
*
)
Parity type
(PARITY)
NONE
ODD (
*
)
EVEN
Stop bit length
(STOP BIT)
1 (
*
)
2
T1.5 character length
(T1.5)
0.1 thr. 5.9 (1.5)
*
3
T3.5 character length
(T3.5)
0.2 thr. 6.0 (3.5)
*
3
NORMAL : Low bit address (word) (
*
)
SWAP : High bit address (word)
Long register
(LONG REG)
MO
DO