ZERO ADJUSTMENT
1) Apply 0% input signal.
2) Hold down [M] for 3 seconds* and push [M] to choose [Z].
3) Press [SET], and the bargraph shows 0%.
■
SPAN ADJUSTMENT
1) Apply 100% input signal.
2) Hold down [M] for 3 seconds* and push [M] to choose [S].
3) Press [SET], and the bargraph shows 100%.
■
ALARM SETPOINT ADJUSTMENTS
•48NAV-2:
H
[L setpoint] to 100%
L
0% to [H setpoint]
No alarm trip is selectable
•48NAV-4:
HH [H setpoint] to 100%
H
[L setpoint] to [HH setpoint]
L
[LL setpoint] to [H setpoint]
LL 0% to [L setpoint]
No alarm trip is selectable
• How to Set LL (or L, H, HH) Setpoints
1) Hold down [M] for 3 seconds* and push [M] to choose
[LL].
2) Press [UP] or [DOWN] buttons until the indicator comes
to the desired position, and press [SET].
(Same procedure for L, H, HH setpoints)
• How to Cancel HH and H Alarms
1) Press [UP] or [DOWN] buttons until the indicator comes
to the upper limit, and press [SET].
HH indicator must be set before H as the H setpoint can-
not go above the HH setpoint.
• How to Cancel LL and L Alarms
1) Press [UP] or [DOWN] buttons until the indicator comes
to the lower limit, and press [SET].
LL indicator must be set before L as the L setpoint can-
not go below the LL setpoint.
* The [M] button remain activated for 1 minute after it has
been used to choose a indicator LED (programming mode).
During this period, pressing the [M] button briefly is enough
to choose another indicator. After 1 minute, it turns to deac-
tivated state.
CALIBRATION PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the indication to a receiving instrument or in
case of regular calibration, adjust the output as explained
in the following.
■
HOW TO CALIBRATE THE OUTPUT INDICATION
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust bargraph to 0% follow-
ing the procedure explained in “ADJUSTMENT PROCE-
DURE.”
2) SPAN: Apply 100% input and adjust bargraph to 100%
following the same procedure.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
MAINTENANCE
Regular checking procedure is explained below:
■
CHECKING
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the bargraph
for the respective input signal remains within accuracy de-
scribed in the data sheet. When the bargraph is out of toler-
ance, recalibrate the unit according to the “CALIBRATION
PROCEDURE” explained earlier.
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protectors for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.