MODEL: 47LT

Cold junction compensation error:
±3°C at 25 ±10°C
±5.4°F at 77 ±18°F
Temp. coefficient: ±0.015%/°C (±0.008%/°F) when theinput
range is set to the maximum span.
Input resolution: Max. 16 bits
Output resolution: Max. 13 bits
Response time: ≤ 0.5 sec.
(alarm output: 0 – 100 % at 90 % setpoint)
≤ 0.5 sec. (DC output: 0 – 90 %)
Burnout response: ≤ 15 sec.
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute (input to DC
output to HH output or H output to L output or LL output to
power to ground)

STANDARDS & APPROVALS

CE conformity:
EMC Directive (2004/108/EC)
  EMI EN 61000-6-4: 2007
  EMS EN 61000-6-2: 2005
Low Voltage Directive (2006/95/EC)
 EN 61010-1: 2001
 Measurement Category II (alarm)
 Installation Category II (power)
 Pollution degree 2
Input to alarm output to power: Reinforced insulation
(300 V)
Input to DC output: Basic insulation (300 V)
Protection against access to the terminal blocks:
Finger protection (VDE 0660-514)

EXTERNAL VIEW

(4) Max/Min Button

(5) Alarm/    Button

(6) Init/    Button

(7) Shift Button

(8) Up Button

(1) Main Display

(2) Alarm Indicators

(3) Function Indicators

Alarm/

Init/

Max/Min

Shift

Up

Ini

HH

H

P

L

LL

Alm

D/P

Adj

Fnc

Min

Max

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Содержание 47LT

Страница 1: ...ue W White 4 POWER INPUT AC Power M2 100 240 V AC Operational voltage range 85 264 V 50 60 Hz DC Power R 24 V DC Operational voltage range 24 V 10 ripple 10 p p max P 110 V DC Operational voltage rang...

Страница 2: ...resistance 1 M minimum Burnout sensing 0 1 A Default input type K CA Temperature Range THERMOCOUPLE CONFORMANCE USABLE RANGE RANGE PR C 0 to 1700 30 to 1730 F 32 to 3092 22 to 3146 K CA C 200 to 1300...

Страница 3: ...formity EMC Directive 2004 108 EC EMI EN 61000 6 4 2007 EMS EN 61000 6 2 2005 Low Voltage Directive 2006 95 EC EN 61010 1 2001 Measurement Category II alarm Installation Category II power Pollution de...

Страница 4: ...each setting mode 7 Shift button Used to move on to the setting standby status and shift through display digits in each setting item 8 Up button Used to change setting values Refer to the instruction...

Страница 5: ...TS unit mm 92 0 8 0 45 0 6 0 min 120 min 75 Panel thickness 1 6 to 8 0 mm Ruggh lzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www sentronic com Produkte S...

Страница 6: ...isplay Setting A D Converter T C comp leadwire 1 3 2 5 6 4 CJC SENSOR metal leg DC OUTPUT 7 8 Isolation Output Driver Digital Computation Display Setting A D Converter T C comp leadwire 1 3 2 5 6 11 1...

Страница 7: ...Specifications are subject to change without notice Ruggh lzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www sentronic com Produkte Support und Service SE...

Отзывы: