MODEL: 47LT

Digital Panel Meters 47 Series

THERMOCOUPLE INPUT DIGITAL PANEL METER

(4-digit, LED display type)
Functions & Features
• 4-digit thermocouple input digital panel meter
• 1/8 DIN size
• Moving average function to suppress the display flickering
• Max. and Min. value display
• IP66 front panel
• Separable terminal block
• Rear terminal cover for safety strapped to the meter

Alarm/

Init/

Max/Min

Shift

Up

Ini

Alm

D/P

Adj

Fnc

Min

Max

HH
H
P

L

LL

48

(1.89)

mm (inch)

96 (3.78)

98.5 (3.88)

MODEL: 47LT-1[1][2][3]-[4][5]

ORDERING INFORMATION

• Code number: 47LT-1[1][2][3]-[4][5]
Specify a code from below for each [1] through [5].
(e.g. 47LT-101G-M2/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01/SET)

INPUT – Field-selectable

1: (PR), K (CA), E (CRC), J (IC), T (CC), B (RH), R, S, N

[1] DC OUTPUT

0: Without

Current

A: 4 – 20 mA DC (Load resistance 550 Ω max.)
D: 0 – 20 mA DC (Load resistance 550 Ω max.)

Voltage

4: 0 – 10 V DC (Load resistance 10 kΩ min.)
5: 0 – 5 V DC (Load resistance 5000 Ω min.)
6: 1 – 5 V DC (Load resistance 5000 Ω min.)
4W: -10 – +10 V DC (Load resistance 10 kΩ min.)

[2] ALARM OUTPUT

0: None
1: N.O. relay contact, 4 points
2: SPDT relay contact, 2 points

[3] DISPLAY COLOR

R: Red
YR: Orange
G: Green
BG: Bluegreen
B: Blue
W: White

[4] POWER INPUT

AC Power

M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 50/60 Hz)

DC Power

R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)

[5] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)

Moving parts and indicators are not coated.
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

TERMINAL SCREW MATERIAL

/S01: Stainless steel

EX-FACTORY SETTING

/SET: Preset according to the Ordering Information Sheet
 (No. ESU-9512)

GENERAL SPECIFICATIONS

Construction: Panel flush mounting
Degree of protection: IP66; applicable to the front of the
panel meter mounted according to the specified panel
cutout
Connection: M3 screw terminals (torque 0.6 N·m)
Screw terminal: Nickel-plated steel (standard) or stainless
steel
Housing material: Flame-resistant resin (gray)
Isolation: Input to DC output to HH output or H output to
 L output or LL output to power
Burnout: Upscale standard; downscale optional by
programming
Setting: (Front button)
• Input type
• Alarm setpoint
• Hysteresis (deadband)

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Содержание 47LT

Страница 1: ...ue W White 4 POWER INPUT AC Power M2 100 240 V AC Operational voltage range 85 264 V 50 60 Hz DC Power R 24 V DC Operational voltage range 24 V 10 ripple 10 p p max P 110 V DC Operational voltage rang...

Страница 2: ...resistance 1 M minimum Burnout sensing 0 1 A Default input type K CA Temperature Range THERMOCOUPLE CONFORMANCE USABLE RANGE RANGE PR C 0 to 1700 30 to 1730 F 32 to 3092 22 to 3146 K CA C 200 to 1300...

Страница 3: ...formity EMC Directive 2004 108 EC EMI EN 61000 6 4 2007 EMS EN 61000 6 2 2005 Low Voltage Directive 2006 95 EC EN 61010 1 2001 Measurement Category II alarm Installation Category II power Pollution de...

Страница 4: ...each setting mode 7 Shift button Used to move on to the setting standby status and shift through display digits in each setting item 8 Up button Used to change setting values Refer to the instruction...

Страница 5: ...TS unit mm 92 0 8 0 45 0 6 0 min 120 min 75 Panel thickness 1 6 to 8 0 mm Ruggh lzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www sentronic com Produkte S...

Страница 6: ...isplay Setting A D Converter T C comp leadwire 1 3 2 5 6 4 CJC SENSOR metal leg DC OUTPUT 7 8 Isolation Output Driver Digital Computation Display Setting A D Converter T C comp leadwire 1 3 2 5 6 11 1...

Страница 7: ...Specifications are subject to change without notice Ruggh lzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www sentronic com Produkte Support und Service SE...