47D Series Modbus Reference Guide EM-9501-C Rev.4
3.8.2 SETPOINTS & BANK SWITCHING
Bank 1 (Register 4102 ... 4113) is used when Bank Switching is disabled.
ADDR. WORD CONTENTS
UNIT
4101
1
Select Bank No.
1... 8
Factory setting : 1
4102
1
Bank 1: LL Enable
0 : Disable
1 : Enable (*)
4103
2
Bank 1: LL setpoint
-20000 ... 100000
V M AC
V M AC
Decimal point position setting
-99999 ... 999999
T R
T R
°C/100 or °F/100
Factory setting :
VV
14000 /
VA
5600 /
T
2000 /
R
2000 /
M
-8000 /
AC
2000/2000
4105
1
Bank 1: L Enable
0 : Disable
1 : Enable (*)
4106
2
Bank 1: L setpoint
-20000 ... 100000
V M AC
V M AC
Decimal point position setting
-99999 ... 999999
T R
T R
°C/100 or °F/100
Factory setting :
VV
22000 /
VA
8800 /
T
3000 /
R
3000 /
M
-4000 /
AC
6000/6000
4108
1
Bank 1: H Enable
0 : Disable
1 : Enable (*)
4109
2
Bank 1: H setpoint
-20000 ... 100000
V M AC
V M AC
Decimal point position setting
-99999 ... 999999
T R
T R
°C/100 or °F/100
Factory setting :
VV
38000 /
VA
15200 /
T
7000 /
R
7000 /
M
4000 /
AC
14000/14000
4111
1
Bank 1: HH Enable
0 : Disable
1 : Enable (*)
4112
2
Bank 1: HH setpoint
-20000 ... 100000
V M AC
V M AC
Decimal point position setting
-99999 ... 999999
T R
T R
°C/100 or °F/100
Factory setting :
VV
46000 /
VA
18400 /
T
8000 /
R
8000 /
M
8000 /
AC
18000/18000
4114
12
Bank 2 setpoints
:
Identical to Bank 1 setting (4102 ... 4112)
4125
4126
12
Bank 3 setpoints
:
Identical to Bank 1 setting (4102 ... 4112)
4137
4138
12
Bank 4 setpoints
:
Identical to Bank 1 setting (4102 ... 4112)
4149
4150
12
Bank 5 setpoints
:
Identical to Bank 1 setting (4102 ... 4112)
4161
4162
12
Bank 6 setpoints
:
Identical to Bank 1 setting (4102 ... 4112)
4173
4174
12
Bank 7 setpoints
:
Identical to Bank 1 setting (4102 ... 4112)
4185
4186
12
Bank 8 setpoints
:
Identical to Bank 1 setting (4102 ... 4112)
4197